2016-03-04 11:06:31COMMENTS:
 LICENSED FIRE ALARM CONTRACTOR IS REQUIRED TO SUBMIT
 SHOP DRAWINGS THAT INCLUDE A STAMPED APPROVAL BY THE
 ENGINEER OF RECORD, VOLTAGE CALCULATIONS, BATTERY
 CALCULATIONS, ALL WIRE SIZES AND TYPES, AND ALL DEVICE
 TYPES AND LOCATIONS FOR APPROVAL PRIOR TO THE
 INSTALLATION OF ANY PART OF THE SYSTEM. FIRE ALARM
 INSTALLATION SHALL COMPLY WITH NFPA 70 AND 72, STATE
 AND LOCAL ORDINANCES.
  
 NFPA 72-17.14.5: MANUAL FIRE ALARM BOXES SHALL BE
 INSTALLED SO THAT THEY ARE CONSPICUOUS, UNOBSTRUCTED,
 AND ACCESSIBLE.
 NFPA 72-17.14.6: MANUAL FIRE ALARM BOXES SHALL BE
 LOCATED WITHIN 60 IN. (1.52 M) OF THE EXIT DOORWAY
 OPENING AT EACH EXIT ON EACH FLOOR.
  
 LICENSED FIRE SPRINKLER CONTRACTOR IS REQUIRED TO
 SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO
 INSTALLATION. FIRE SPRINKLER INSTALLATION SHALL COMPLY
 WITH NFPA 13, STATE AND LOCAL ORDINANCES.
  