| 2016-05-02 19:40:31 | ELECTRICAL REVIEW COMMENTS |
| | |
| | CORRECTIONS REQUIRED: |
| | THERE CONTINUES TO BE NUMEROUS ABNORMALITIES WITH THIS |
| | SUBMITTAL. IT IS NOT MY INTENT TO GENERATE A PUNCH FOR |
| | THE DESIGNER. JUST TO NAME A FEW OF THE DEFICIENCIES |
| | NOTED, THE SCOPE OF WORK AS DEFINED FOR THIS REVISION |
| | ALONG WITH THE SCOPE OF WORK DESCRIBED ON THE MASTER |
| | PERMIT DO NOT MATCH WHAT IS INDICATED ON THE SUBMITTED |
| | DRAWINGS. THOUGH THE RISER DIAGRAM HAS BEEN REVISED TO |
| | INDICATE A SINGLE METER, THE ELECTRICAL PANELS |
| | REFERENCED ARE NOT SHOWN ON THE FLOOR PLANS. YOU |
| | SUBMITTED LOAD CALCS FOR A 150 AMP PANEL NOT SHOWN ON |
| | THE RISER DIAGRAM. THE RISER DIAGRAM IS INDICATED TO BE |
| | 300 AMP WITH A 200 AMP RATED CONDUCTOR. |
| | YOU NEED TO SUBMIT A SITE SPECIFIC RISER DIAGRAM AS |
| | INDICATED IN NEC 215.5. |
| | THE ELECTRICAL OUTLETS AND LIGHTING AS SHOWN ON THE |
| | FLOOR PLAN FOR BLDG. 1 FAIL TO MEET MINIMUM CODE |
| | REQUIREMENTS AS WELL. VERIFY OUTLET SPACING AS |
| | INDICATED IN NEC 210.52. PLEASE REMEMBER TO PROVIDE |
| | PROPER ILLUMINATION ABOUT THE ELECTRICAL PANEL. |
| | PLEASE NOTE THAT THIS IS NOT THE FIRST TIME THIS COMES |
| | UP FOR REVIEW. THE MASTER PERMIT WAS REVIEWED 6 TIMES |
| | AND STILL NEVER WAS PROPERLY PRESENTED. |
| | AT THIS TIME I WOULD LIKE TO MAKE YOU AWARE OF THE |
| | FOLLOWING: |
| | PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT |
| | WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY |
| | PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON |
| | ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A |
| | PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO |
| | THE NORMAL FEE |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |