| 2016-04-12 15:09:00 | ELECTRICAL REVIEW COMMENTS |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 2010 FLORIDA BLDG. CODES; 2008 NEC |
| | |
| | CORRECTIONS REQUIRED |
| | ACCORDING TO THE PROPERTY APPRAISER THIS SITE IS ZONED |
| | AS SINGLE FAMILY AND UNTIL ZONING TELLS ME OTHERWISE A |
| | SECOND OR THIRD ELECTRICAL METER TO THIS SITE WILL NOT |
| | BE AUTHORIZED. IF MORE THAN A SINGLE METER IS |
| | AUTHORIZED, FPL STANDARDS PERMIT ONLY A SINGLE DROP PER |
| | LOT AND NEC HAS FURTHER LIMITATIONS SUCH AS THE |
| | GROUPING OF ALL DISCONNECTS; AND A SINGLE SERVICE TO A |
| | BLDG. AS WELL. THEREFORE, YOU SHALL REVISE THE SERVICE |
| | RISER DIAGRAM ACCORDINGLY. |
| | THAT BEING SAID AND ADDRESSED, THERE ARE FURTHER ISSUES |
| | TO COMPLY WITH SHOULD THE SERVICE MATTER GET SOLVED. |
| | NEC 314.27(D) REQUIRES THAT ALL CEILING BOXES USED TO |
| | SUPPORT PADDLE FANS BE LISTED FOR THE PURPOSE. |
| | NEC 110.26(D) REQUIRES THERE BE PROPER ILLUMINATION |
| | ABOUT THE ELECTRICAL PANEL. |
| | NEC 210.52(F) REQUIRES THAT A LAUNDRY CIRCUIT BE |
| | PROVIDED AND INCLUDED IN THE LOAD CALCS AND INCLUDED IN |
| | THE PANEL SCHEDULE. |
| | FBC-E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50% OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| | SHALL BE HIGH-EFFICACY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |