| Date |
Text |
| 2016-03-22 10:44:11 | 1ST REVIEW: FBC 2014 5TH ED |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BLDG. PLANS EXAMINER ? PX3169 |
| | (561) 805-6718 |
| | [email protected] |
| | |
| | 1. PROVIDE SITE PLAN. |
| | 2. PROVIDE ENERGY CALC'S. |
| | 3. PROVIDE DETAIL FOR NEW MASONRY OPENINGS IN EXISTING |
| | CMU WALLS. |
| | 4. PROVIDE SHORING PLAN FOR REMOVAL OF EXISTING CMU |
| | LOAD BEARING WALLS PER NOTE 2, PG. S-1. |
| | 5. SPECIFY SPACING OF HORIZ. JOINT RE-INFORCING @ 8" |
| | CMU WALLS PER DETAIL 5, PG. S-1. |
| | 6. IDENTIFY LENGTH OF #4 DOWELS IN NOTE # 2, FOUNDATION |
| | PLAN, PG. S-1. |
| | 7. IMPACT FEES. |
| | 8. PROVIDE FLOOR PLAN. IDENTIFY INTENDED USE OF SPACE. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE |
| | SETBACKS AND BUILDING SEPARATION. |
| | |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND |
| | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED |
| | WITH A COPY OF RECEIPT AS APPLICABLE. |
| | |
| | |