| Plan Review Notes For Permit 16020955 |
| Permit Number |
16020955 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-04 18:59:32 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PRODUCT APPROVALS ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD. | | | | | | 2) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE FABRIC IMPACT PROTECTION SYSTEM. | | | | | | 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE | | | COMPLIANCE CERTIFICATION. | | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | | | | |
|