| Plan Review Notes For Permit 16020955 |
| Permit Number |
16020955 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-09 17:20:39 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE PLUMBING RISER DIAGRAM IS NOT DRAWN CORRECTLY. | | | DRAW THE DIAGRAM ON THE SAME PLANE. THE WAY IT IS DRAWN | | | IT APPEARS THAT THE TUB IS ON THE SECOND FLOOR AT THE | | | FIRST BATHROOM AND THE SHOWER AND DOUBLE VANITY ARE ON | | | THE FLOOR ABOVE THE CLOTHES WASHER. | | | | | | 3) THE CLOTHES WASHER REQUIRES A SEPARATE VENT AND IS | | | REQUIRED TO TIE IN DOWN STREAM OF THE BATHROOM GROUP. | | | IT CAN NOT BE WET VENTED AS SHOWN. FBCR-P3108. IT | | | REQUIRES A MINIMUM 2" VENT, TRAP AND DRAIN PIPE. FBCR - | | | P3005.4, P3102.3, P3201.7 | | | | | | 4) THE SHOWER AND TUB ARE REQUIRED TO CONNECT | | | HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET VENTED. | | | FBCR-P3108.1 | | | | | | 5) THE SHOWER IS REQUIRED TO HAVE A MINIMUM 1-1/2 INCH | | | TRAP AND FIXTURE DRAIN BASED ON A FLOW RATE OF 5.7 GPM | | | OR LESS. FBCR-P3201.7 | | | | | | 6) THE TUB IS REQUIRED TO HAVE A MINIMUM 1-1/2 INCH | | | TRAP AND FIXTURE DRAIN. FBCR-P3201.7 |
|