| 2016-03-09 17:21:46 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) SMOKE ALARMS ARE REQUIRED PER FBC-R 314.3.1. | | | | | | 3) A MINIMUM OF ONE 20 AMP BRANCH CIRCUIT IS REQUIRED | | | TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). FBCR-E3703.4 |
|