| Plan Review Notes For Permit 16020948 |
| Permit Number |
16020948 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-14 15:48:16 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020948 | | | 3/14/16 | | | | | | 1) IDENTIFY THE ROOMS, AND PROVIDE ROOM DIMENSIONS ON | | | THE AC LAYOUT PLANS. | | | 2) PROVIDE A NORTH DIRECTIONAL ARROW ON THE AC PLANS. | | | 3) INDICATE THE SEER OF THE AC SYSTEM ON THE PLANS, AND | | | SUBMIT AN AHRI CERTIFICATE. | | | 4) IT APPEARS THAT THE AHU IS IN THE ATTIC SPACE- | | | PLEASE SHOW AN ACCESS PANEL ON THE PLAN, AND PROVIDE | | | DETAILS IN ACCORDANCE WITH SECTION M1305.1.3 FBC-14 | | | RESIDENTIAL, AND SECTION R403.2.4 FBC-14 ENERGY | | | CONSERVATION. | | | 5) PROVIDE A RETURN AIR SYSTEM THAT MEETS COMPLIANCE | | | WITH SECTION M1602.1, AND M1602.4 FBC-14 RESIDENTIAL. | | | 6) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR TIE DOWN | | | OF THE AC CONDENSER AND CONSTRUCTION OF THE CONDENSER | | | PAD- | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|