| 2016-03-09 15:58:23 | 1ST REVIEW: FBC 2014 5TH ED |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BLDG. PLANS EXAMINER ? PX3169 |
| | (561) 805-6718 |
| | [email protected] |
| | |
| | 1. PROVIDE DETAIL FOR CMU INFILL WALL AT GARAGE DOOR |
| | OPENING. INCLUDE VERTICAL AND HORIZONTAL RE-INFORCING |
| | AND CONNECTION TO EXISTING SLAB AND BEAM. |
| | |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE PLEASE BE ADVISED |
| | THE INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO |
| | BE MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE |
| | ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK |
| | PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117. |
| | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| | PURPOSES UNTIL APPROVED. |
| | REQUIRED TESTS ARE TO BE MADE AT THE EXPENSE OF THE |
| | OWNER, OR AGENT, BY AN APPROVED TESTING LABORATORY OR |
| | OTHER APPROVED AGENCY. |
| | |
| | 2. PROVIDE PRODUCT APPROVALS FOR IMPACT FIXED GLASS. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| | |
| | 3. BASED ON THE REQUIREMENTS OF THE EXISTING BUILDING |
| | CODE, SEC R322, IT MUST BE ESTABLISHED WHAT LEVEL OF |
| | WORK WILL BE REQUIRED. PROVIDE DOCUMENTATION |
| | ESTABLISHING "MARKET VALUE" OF THE RESIDENCE SO IT CAN |
| | BE DETERMINED IF THE PROPOSED IMPROVEMENTS EXCEED 50% |
| | OF MARKET VALUE. THE LEVEL OF WORK REQUIRED WILL BE |
| | DETERMINED BY THIS INFORMATION. SEE BELOW. |
| | |
| | [B] 402.2 FLOOD HAZARD AREAS. |
| | FOR BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS |
| | ESTABLISHED IN SECTION 1612.3 OF THE FLORIDA BUILDING |
| | CODE, BUILDING OR SECTION R322 OF THE FLORIDA BUILDING |
| | CODE, RESIDENTIAL, AS APPLICABLE, ANY ADDITION THAT |
| | CONSTITUTES SUBSTANTIAL IMPROVEMENT OF THE EXISTING |
| | STRUCTURE, AS DEFINED IN SECTION 202, SHALL COMPLY WITH |
| | THE FLOOD DESIGN REQUIREMENTS FOR NEW CONSTRUCTION, AND |
| | ALL ASPECTS OF THE EXISTING STRUCTURE SHALL BE BROUGHT |
| | INTO COMPLIANCE WITH THE REQUIREMENTS FOR NEW |
| | CONSTRUCTION FOR FLOOD DESIGN. |
| | |
| | FOR BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS |
| | ESTABLISHED IN SECTION 1612.3 OF THE FLORIDA BUILDING |
| | CODE, BUILDING, OR SECTION R322 OF THE FLORIDA BUILDING |
| | CODE, RESIDENTIAL, AS APPLICABLE ANY ADDITIONS THAT DO |
| | NOT CONSTITUTE SUBSTANTIAL IMPROVEMENT OF THE EXISTING |
| | STRUCTURE, AS DEFINED IN SECTION 202, ARE NOT REQUIRED |
| | TO COMPLY WITH THE FLOOD DESIGN REQUIREMENTS FOR NEW |
| | CONSTRUCTION. |
| | |
| | FBC 202 |
| | SUBSTANTIAL IMPROVEMENT. ANY REPAIR, RECONSTRUCTION, |
| | REHABILITATION, ALTERATION, ADDITION OR OTHER |
| | IMPROVEMENT OF A BUILDING OR STRUCTURE, THE COST OF |
| | WHICH EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET VALUE |
| | OF THE STRUCTURE BEFORE THE IMPROVEMENT OR REPAIR IS |
| | STARTED. IF THE STRUCTURE HAS SUSTAINED SUBSTANTIAL |
| | DAMAGE, ANY REPAIRS ARE CONSIDERED SUBSTANTIAL |
| | IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK |
| | PERFORMED. |
| | |
| | |