| Plan Review Notes For Permit 16020945 |
| Permit Number |
16020945 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-08 15:28:42 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | NEC 230.70(A)(1)/E3601.6.2 -THE SERVICE DISCONNECTING | | | MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE | | | LOCATION EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR | | | INSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE | | | CONDUCTORS. UNLESS FEEDER RACEWAYS ARE BEING RANNED | | | UNDERGROUND THEN THEY ARE CONSIDERED OUTSIDE THE | | | BUILDING | | | | | | NEC 210.12B/E3902.12 - OUTLETS TO BE AFCI PROTECTED ( | | | MAKE A NOTE ) | | | | | | FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN | | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE | | | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE | | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN | | | ONLY HIGH EFFICACY LAMPS. | | | | | | FBC-E R402.4.8 RECESSED LIGHTING. RECESSED LIGHTING | | | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC | | | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN | | | CONDITIONED & UNCONDITIONED SPACES. |
|