| 2016-03-16 15:01:25 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO AND |
| | COMMENTS BELOW MAY BE ADDRESSED AFTER THE PERMIT IS |
| | ISSUED. FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO |
| | OPTION IS PREFERRED AT THIS TIME. OTHERWISE, RE-SUBMIT |
| | PACKAGE ADDRESSING THE COMMENTS. COUNTY IMPACT FEES |
| | ASSESSMENT IS REQUIRED PRIOR TO ISSUING THE PERMIT. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- EXTERIOR WALL SECTION "C" ON SHEET S101: |
| | A) SPECIFY HOW ARE THE NEW 2 X 6 STUDS ATTACHED TO THE |
| | TOP AND TO THE BOTTOM PLATES. SEC. R801.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) SPECIFY THE MIN. STUCCO THICKNESS AS REQUIRED BY |
| | TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | C) 4" CLEARANCE FROM FINISHED GRADE TO STUCCO DOESN'T |
| | COMPLY WITH SEC. R318.7 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). REVISE AS REQUIRED. |
| | |
| | 3- BREEZEWAY ROOF DETAIL "A" ON SHEET S102 AND SHEET |
| | A300: |
| | A) SPECIFY THE ROOF SLOPE AS REQUIRED BY SEC. R905.11.1 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) SPECIFY SOFFIT VENT SIZE AND SPACING. SEC. R806 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- SHEET A300: CLARIFY HOW PROVIDING R-30 CLOSED CELL |
| | INSULATION ON 2X6 WALLS. PROVIDE MANUFACTURER'S SPECS |
| | SHOWING REQUIRED THICKNESS TO MEET THE R-30 VALUE. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE, ENERGY |
| | CALCULATIONS ARE NOT REQUIRED. IF CONTRACTOR WANTS THE |
| | ENERGY CALCULATIONS SUBMITTED FOR REVIEW, THEN THEY |
| | NEED TO BE REVISED AS FOLLOWS: |
| | A) OWNER/AGENT TO CERTIFY BOTTOM OF FORM AS REQUIRED BY |
| | SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | B) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER. SEC. R101.5.1.1.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD SUBMITTED AS REQUIRED BY SEC. |
| | R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | D) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE |
| | ORIENTATION, AREA AND OVERHANG DEPTH AND SEPARATION |
| | DON'T MATCH PLANS. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| | WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING |
| | THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 6- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| | CREDIT. SPECIFY ON PLANS THE CEILING FAN SIZE ON EACH |
| | ROOM AS REQUIRED BY TABLE R405.7.6 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) SLIDING GLASS DOORS AS SHOWN ON PLANS. DRAWINGS |
| | SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL8753-R3 ARE |
| | FOR SMALL MISSILE IMPACT PROTECTION. NEED DOORS WITH |
| | LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) CASEMENT WINDOWS AS SHOWN ON PLANS. DRAWINGS |
| | SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL9968-R4 ARE |
| | FOR SMALL MISSILE IMPACT PROTECTION. NEED WINDOWS WITH |
| | LARGE MISSILE IMPACT PROTECTION. SEC. R301.2.1.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | C) SHINGLES AS SPECIFIED ON PLANS (IF RE-ROOFING THE |
| | GUEST HOUSE). |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | ENGINEER TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO |
| | EACH CONNECTOR. |
| | |
| | 8- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE NEW WATER FEATURE STRUCTURE SHOWN |
| | ON SITE PLAN SHEET SP01. SEC. R301 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | 10- BREEZEWAY FLAT ROOF NOA 12-0601.10 SUBMITTED: |
| | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE USED. |
| | SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T |
| | STAPLE OLD DRAWINGS TO NEW SET. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |