| 2016-03-01 11:58:30 | 1) THE WATER SUPPLY VALVES FOR THE STACKED WASHER AND | | | DRYER UNITS ON THE FIRST FLOOR LAUNDRY (#112) SHALL BE | | | ACCESSIBLE. THE VALVES CANNOT BE LOCATED BEHIND THE | | | UNIT UNLESS AN ACCESS PANEL IS PROVIDED IN THE STACKED | | | UNIT. 2014 FBCR SEC. P2903.9.3. | | | 2) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS | | | PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS | | | AREA. | | | 3) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS | | | PLAN. | | | 4) SUBMIT A ROOF DRAIN RISER DIAGRAM FOR THE ROOF | | | DRAINS ON THE FLAT ROOF. SHOW THE SQUARE FOOTAGE THAT | | | DRAINS INTO EACH ROOF DRAIN. INCLUDE 1/2 THE AREA OF | | | THE PARAPET WALL. DRAINS SHALL DISCHARGE A MINIMUM OF 1 | | | FT. FROM THE EXTERIOR BUILDING WALL. 2014 FBCR SEC. | | | R318.5. STORM DRAINAGE SHALL BE DESIGNED USING TABLE | | | 1106.3. | | | 5) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE | | | WITH 2014 FBCR SEC.R903.4.1. | | | 6) THE GAS WATER HEATER IN THE GARAGE SHALL BE | | | PROTECTED FROM PHYSICAL DAMAGE. | | | 7) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE | | | WITH 2014 FBCR SEC.G2404.3. | | | 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS | | | APPLIANCES. 2014 FBCR SEC.G2407. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|