| Plan Review Notes For Permit 16020935 |
| Permit Number |
16020935 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-23 14:24:40 | 107.2.1.3 ADDITIONAL DATA. CONFIRM CFM QUANTITIES AND | | | SIZES OF BATHROOM EXHAUST FAN DUCTS. AS PER PLANS EACH | | | FAN SPECIFIES 105 CFM @ .3 STATIC PRESSURE. PROVIDE CFM | | | QUANTITIES PER BATHROOM. 4" DUCT AS PER TRANE DUCULATOR | | | IS 70 CFM AT .3 STATIC PRESSURE. CHECK ALL EXH FANS. | | | CHECK EXH FAN #6 & #7 HEADERS AND RISER TO ROOF JACK. | | | MAKE CORRECTIONS AND RESUBMIT. |
|