Plan Review Notes
Plan Review Notes For Permit 16020935
Permit Number 16020935
Review Stop G
Sequence Number 1
Notes
Date Text
2016-03-01 12:07:231) SHT. A-100 - THE AREA AT THE OUTDOOR GRILL IS
 PARTIALLY CUT OFF. SUBMIT THE COMPLETE LAYOUT FOR THIS
 AREA.
 2) SHT.P-1 - THE POOL HEATER IS NOT SHOWN ON THE GAS
 PLAN.
 3) THE GAS WATER HEATER IN THE GARAGE SHALL BE
 PROTECTED FROM PHYSICAL DAMAGE.
 4) ALL GAS APPLIANCES SHALL BE LISTED IN ACCORDANCE
 WITH 2014 FBCR SEC.G2404.3.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES. 2014 FBCR SEC.G2407.
 6) SIZE ALL GAS LINES DOWNSTREAM OF THE REGULATORS AT
 EACH APPLIANCE. FBC 107.2.1.
  