Plan Review Notes
Plan Review Notes For Permit 16020935
Permit Number 16020935
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-10 09:03:50INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A NOTE TO PLANS TO INDICATE SEPARATE
 PERMIT REQUIREMENTS FOR ALL LOW VOLTAGE SYSTEMS,
 GENERATOR, ELEVATOR, DOCK AND POOL.
 2. PROVIDE GENERAL NOTE TO INDICATE REQUIRED TAMPER
 RESISTANT RECEPTACLES PER FBC RES E4002.14
 3. PROVIDE GENERAL NOTE TO INDICATE FBC EC R404.1 75%
 OF LAMPS TO BE HIGH EFFICACY LAMPS.
 4. PROVIDE MANUF. DATA SHEET FOR THE PHASE CONVERTER.
 FBC 107.3.5
 5. LABEL THE AVAILABLE FAULT CURRENT AT THE TRANSFORMER
 AND PROVIDE AIC CALCULATION FOR THE SERVICE SHOWN. FBC
 RES E3606.3
 6. LABEL MAIN DISTRIBUTION PANEL TO RATED FOR SERVICE
 ENTRANCE PER FBC RES E3606.4
 7. DELETE EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM
 METER TO MDP AS PER FBC RES E3607 GROUNDED CONDUCTOR
 NOT TO BE PARALLELED.
 8. ADD A NOTE TO RISER DIAGRAM TO INDICATE THAT THE
 GENERATOR IS A NON-SEPARATELY DERIVED SYSTEM. FBC
 107.3.5
 9. ADD A FIXTURE LEGEND FOR REFERENCE PURPOSE. FBC
 107.3.5
 10. LABEL CU-1 TO CORRELATE WITH MECHANICAL SHEETS.
 SHOWN AS AHU 1A AND 1B ON ELECTRICAL SHEETS.
 11. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  