| Plan Review Notes For Permit 16020930 |
| Permit Number |
16020930 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-29 11:10:52 | PASSED WITH A PROVISO | | | | | | NEC 210.70 A2B LIGHTING OUTLET REQUIRED FOR DWELLING | | | UNIT EXTERIOR DOOR ILLUMINATION. | | | | | | NEC 250.94 PROVIDE INTERSYSTEM BONDING STRIP AT SERVICE | | | | | | NEC 406.11 TAMPER RESISTANT RECEPTACLES REQUIRED | | | |
|