Plan Review Notes
Plan Review Notes For Permit 16020929
Permit Number 16020929
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-26 10:13:31PROVIDE MORE INFORMATION
  
 1) SHOW LOCATION OF CONDENSER. IF CONDENSER IS ON THE
 ROOF
 PROVIDE TIE DOWN DETAILS FROM THE ENGINEER ( STAND TO
 ROOF
 AND EQUIPMENT TO STAND) 301.15 WIND RESISTANCE 2014 FBC
 (M)
 2) SHOW LOCATION OF THE COOLER ON THE PLAN. IF THE
 COOLER IS
 OUT SIDE THE BUILDING PROVIDE WIND LOAD CALCULATIONS.
 3) PROVIDE COOLER INSTALLATION INSTRUCTIONS WITH THE
 PLAN
 SECTION 107 FBC 2014.
 TRIED TO CALL CONTRACTOR COULD NOT READ PHONE NUMBER
 ON THE APPLICATION.
  