| Plan Review Notes For Permit 16020914 |
| Permit Number |
16020914 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-04 06:35:53 | PLAN DENIED | | | 1) PLEASE SHOW HOW YOU ARE GOING TO MEET THE | | | REQUIREMENT | | | OF SECTION 508.1.1 MAKE UP AIR TEMPERATURE 2014 FBC (M) | | | 2) INSTALLATION SHALL COMPLY WITH THE FBC 2014 (M) NOT | | | 2010 | | | 3) PLEASE SHOW HOW THE DUCT OUTSIDE OF THE BUILDING | | | WILL MEET | | | THE REQUIREMENTS OF 301.15 WIND RESISTANCE 2014 FBC (M) | | | 4) REFER TO SECTION 506.3.6GREASE DUCT CLEARANCES | | | 2014 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|