Plan Review Notes
Plan Review Notes For Permit 16020914
Permit Number 16020914
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-04 06:35:53PLAN DENIED
 1) PLEASE SHOW HOW YOU ARE GOING TO MEET THE
 REQUIREMENT
 OF SECTION 508.1.1 MAKE UP AIR TEMPERATURE 2014 FBC (M)
 2) INSTALLATION SHALL COMPLY WITH THE FBC 2014 (M) NOT
 2010
 3) PLEASE SHOW HOW THE DUCT OUTSIDE OF THE BUILDING
 WILL MEET
 THE REQUIREMENTS OF 301.15 WIND RESISTANCE 2014 FBC (M)
 4) REFER TO SECTION 506.3.6GREASE DUCT CLEARANCES
 2014 FBC (M)
  