| Plan Review Notes For Permit 16020902 |
| Permit Number |
16020902 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-05 06:33:04 | 1) PLACE THE OCCUPANCY TYPE OF THE BUILDING ON THE | | | PLANS IN ACCORDANCE WITH CHAPT. 3 OF THE 2014 FBC. | | | 2) THE NEW TOILET ROOM SHALL COMPLY WITH THE FL. | | | ACCESSIBILITY CODE SEC.213.1, 213.2.SUBMIT THE INSIDE | | | CLEAR DIMENSIONS FOR THE TOILET ROOM AND SHOW THE | | | REQUIRED FLOOR CLEARANCES FOR THE PLUMBING FIXTURES PER | | | THE 2014 FAC SECS.305, 604, 606.2. | | | 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. FBC | | | 107.3.5.1.3. | | | 4) SIZE ALL SECTIONS OF THE SANITARY SYSTEM ON BOTH | | | RISERS #1 3 2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|