| Plan Review Notes For Permit 16020902 |
| Permit Number |
16020902 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-08 10:50:34 | NOTES CLEARED WITH DOUG H AND THE OWNER, COMMENTS NOT | | | APPLICABLE | | 2016-03-02 09:46:35 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE PROVIDE A PANEL LOAD SCHEDULE REFLECTING LOADS | | | AND BRANCH CIRCUIT CLEARLY IDENTIFIED FOR NEW EM | | | LIGHTING. FBC 107.3.5 | | | 2.SHOW PER NEC 700.12F THAT UNIT EQUIPMENT IS SERVED | | | FROM THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCH. | | | 3.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE | | | TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU | | | HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|