| Plan Review Notes For Permit 16020863 |
| Permit Number |
16020863 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-01 09:58:24 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020863 | | | 3/1/16 | | | | | | | | | 1) CLARIFY HOW MAKE-UP AIR IS BEING SUPPLIED TO THE | | | DISHWASHER HOOD: NO MUA IN THE SCHEDULE AND NO | | | DEDICATED AC SUPPLY AIR NOTED OR SHOWN. | | | 2) INDICATE COMPLIANCE WITH SECTION 507.9 EXCEPTION FOR | | | THE SS HOOD BACKING TO BE INSTALLED IN AN AREA | | | EXTENDING NOT LESS THAN 18 INCHES IN ALL DIRECTIONS | | | FROM THE HOOD. | | | 3) PROVIDE A ROOF PLAN VIEW SHOWING CLEARANCE DISTANCE | | | MEASUREMENTS FROM THE FANS TO THE ROOF EDGES, AND TO | | | ANY MECHANICAL AND GRAVITY EXHAUST AND AIR INLET | | | LOCATIONS. | | | 4) SUBMIT THE NOA'S FOR THE FANS AND THE DUCT WRAP WITH | | | REVIEW AND APPROVAL SIGNATURES BY THE EOR. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|