| Plan Review Notes For Permit 16020862 |
| Permit Number |
16020862 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-07-14 18:19:00 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND ZONE PRESSURES ON SHEET S.1 HAVE NOT BEEN | | | REVISED TO REFLECT EXPOSURE D. FBCR 301.2.1 | | | | | | 2) THE WIND PRESSURES FOR ROOF ZONE 3 ARE NOT CORRECT | | | IN THE CALCULATIONS THAT WERE SUBMITTED BY THE | | | ENGINEER. ROOF ZONES TWO (2) AND THREE (3) HAVE THE | | | SAME NEGATIVE PRESSURES (-73.08 PSF). THE UPLIFT | | | PRESSURES FOR ROOF ZONE THREE (3) SHOULD BE MORE. FBC | | | R301.2.1 | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | 16' X 8' SECTIONAL GARAGE DOOR +/- 25.5 PSF ARE NOT | | | ADEQUATE. THE PLANS SPECIFY THE REQUIRED PRESSURES FOR | | | THAT DOOR AS +38.7, -42.16 PSF. SUBMIT NEW PRODUCT | | | APPROVALS WITH ADEQUATE DESIGN PRESSURES. FBC R301.2.1 |
|