2016-07-14 18:19:00PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND ZONE PRESSURES ON SHEET S.1 HAVE NOT BEEN
 REVISED TO REFLECT EXPOSURE D. FBCR 301.2.1
  
 2) THE WIND PRESSURES FOR ROOF ZONE 3 ARE NOT CORRECT
 IN THE CALCULATIONS THAT WERE SUBMITTED BY THE
 ENGINEER. ROOF ZONES TWO (2) AND THREE (3) HAVE THE
 SAME NEGATIVE PRESSURES (-73.08 PSF). THE UPLIFT
 PRESSURES FOR ROOF ZONE THREE (3) SHOULD BE MORE. FBC
 R301.2.1
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 16' X 8' SECTIONAL GARAGE DOOR +/- 25.5 PSF ARE NOT
 ADEQUATE. THE PLANS SPECIFY THE REQUIRED PRESSURES FOR
 THAT DOOR AS +38.7, -42.16 PSF. SUBMIT NEW PRODUCT
 APPROVALS WITH ADEQUATE DESIGN PRESSURES. FBC R301.2.1