2016-05-20 18:57:21PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROPOSED STRUCTURE IS LOCATED WITHIN 600 FEET OF
 A LARGE LAKE THAT IS AN EXPOSURE D CONDITION.
 THEREFORE, THE STRUCTURE IS REQUIRED TO BE DESIGNED FOR
 EXPOSURE D. FBC-R 301.2.1.4.3 THE WIND ZONE PRESSURES
 WERE NOT INCREASED TO REFLECT THE CHANGE FROM EXPOSURE
 C TO EXPOSURE D. FBC 301.2.1
  
 2) THE LAST WIND ZONE LISTED ON SHEET S-1 SHOULD BE
 ZONE 5 AND NOT ZONE 3. FBC 107.2.1
  
 3) THE ENERGY COMPLIANCE FORMS ARE REQUIRED TO HAVE THE
 NAME OF THE PERSON THAT PREPARES THEM. FBC ENERGY
 CONSERVATION R405.4.2
  
 4) THE DESIGNER OF RECORD FOR THE PLANS THAT WERE
 SUBMITTED IS JOHN D. HOLT. MR. HOLT'S FLORIDA
 PROFESSIONAL ENGINEER'S LICENSE HAS BEEN SUSPENDED. HE
 CAN NO LONGER SIGN AND SEAL PLANS. A NEW DESIGNER OF
 RECORD IS REQUIRED.
  
 5) THE PRODUCT APPROVAL'S THAT WERE APPROVED IN WRITING
 BY MR. HOLT WILL NEED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE NEW DESIGNER OF RECORD.
  
 6) THE DESIGN LOAD PRESSURES FOR THE PRODUCT APPROVALS
 WILL NEED TO BE CHECKED TO SEE THAT THEY MEET THE
 REVISED OPENING PRESSURES FOR EXPOSURE D SPECIFIED ON
 THE PLANS. FBC-R 301.1
  
  