| Plan Review Notes For Permit 16020862 |
| Permit Number |
16020862 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-20 18:57:21 | PLAN | | | REVIEW COMMENTS | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROPOSED STRUCTURE IS LOCATED WITHIN 600 FEET OF | | | A LARGE LAKE THAT IS AN EXPOSURE D CONDITION. | | | THEREFORE, THE STRUCTURE IS REQUIRED TO BE DESIGNED FOR | | | EXPOSURE D. FBC-R 301.2.1.4.3 THE WIND ZONE PRESSURES | | | WERE NOT INCREASED TO REFLECT THE CHANGE FROM EXPOSURE | | | C TO EXPOSURE D. FBC 301.2.1 | | | | | | 2) THE LAST WIND ZONE LISTED ON SHEET S-1 SHOULD BE | | | ZONE 5 AND NOT ZONE 3. FBC 107.2.1 | | | | | | 3) THE ENERGY COMPLIANCE FORMS ARE REQUIRED TO HAVE THE | | | NAME OF THE PERSON THAT PREPARES THEM. FBC ENERGY | | | CONSERVATION R405.4.2 | | | | | | 4) THE DESIGNER OF RECORD FOR THE PLANS THAT WERE | | | SUBMITTED IS JOHN D. HOLT. MR. HOLT'S FLORIDA | | | PROFESSIONAL ENGINEER'S LICENSE HAS BEEN SUSPENDED. HE | | | CAN NO LONGER SIGN AND SEAL PLANS. A NEW DESIGNER OF | | | RECORD IS REQUIRED. | | | | | | 5) THE PRODUCT APPROVAL'S THAT WERE APPROVED IN WRITING | | | BY MR. HOLT WILL NEED TO BE REVIEWED AND APPROVED IN | | | WRITING BY THE NEW DESIGNER OF RECORD. | | | | | | 6) THE DESIGN LOAD PRESSURES FOR THE PRODUCT APPROVALS | | | WILL NEED TO BE CHECKED TO SEE THAT THEY MEET THE | | | REVISED OPENING PRESSURES FOR EXPOSURE D SPECIFIED ON | | | THE PLANS. FBC-R 301.1 | | | | | | |
|