Plan Review Notes
Plan Review Notes For Permit 16020862
Permit Number 16020862
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-28 13:20:22R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY
 EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY
 IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT
 MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD
 CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN
 SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED
 BY THE MANUFACTURER?S PRODUCT LINES. THE CORRESPONDING
 LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN
 THE CALCULATED LATENT LOAD.
  
 PROVIDE APPROVED HEAT LOAD CACULATIONS AS PER 403.6.1
 AND 403.6.1.1. CONFIRM CFM QUANTITIES. AHU CFM
 QUANTITIES MUST MATCH OR EXCEED CFM QUANTITIES SHOWN ON
 SUPPLY OUTLETS ON PLANS. SPECIFIED UNIT ON EQUIPMENT
 SCHEDULE DOES NOT MEET CFM QUANTITIES SPECIFIED ON
 PLANS FOR SUPPLY OUTLETS. PROVIDE MANUFACTURER DATA
 SHEETS OF EQUIPMENT TO BE INSTALLED.
  
 CONDENSER UNIT MOUNTING DETAIL IS DIFFERENT THAN
 CONDENSER LOCATION NOTES ON PLANS. MAKE CORRECTIONS AS
 PER FBC AND MANUFACTURER SPECIFICATIONS.
  