| 2016-03-28 13:20:22 | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. |
| | |
| | R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY |
| | EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY |
| | IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT |
| | MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD |
| | CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN |
| | SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED |
| | BY THE MANUFACTURER?S PRODUCT LINES. THE CORRESPONDING |
| | LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN |
| | THE CALCULATED LATENT LOAD. |
| | |
| | PROVIDE APPROVED HEAT LOAD CACULATIONS AS PER 403.6.1 |
| | AND 403.6.1.1. CONFIRM CFM QUANTITIES. AHU CFM |
| | QUANTITIES MUST MATCH OR EXCEED CFM QUANTITIES SHOWN ON |
| | SUPPLY OUTLETS ON PLANS. SPECIFIED UNIT ON EQUIPMENT |
| | SCHEDULE DOES NOT MEET CFM QUANTITIES SPECIFIED ON |
| | PLANS FOR SUPPLY OUTLETS. PROVIDE MANUFACTURER DATA |
| | SHEETS OF EQUIPMENT TO BE INSTALLED. |
| | |
| | CONDENSER UNIT MOUNTING DETAIL IS DIFFERENT THAN |
| | CONDENSER LOCATION NOTES ON PLANS. MAKE CORRECTIONS AS |
| | PER FBC AND MANUFACTURER SPECIFICATIONS. |
| | |