| 2016-03-03 13:35:42 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE ADD A RECEPTACLE FOR WALL SPACE IN MASTER | | | BEDROOM, UNDER 2GANG SWITCH SHOWN. FBC RES E3901.2.2 | | | 2.PROVIDE ON PANEL SCHEDULE THE AIC RATING OF | | | EQUIPMENT. | | | 3.SHOW ON ELECTRICAL CALCULATION 2- 1500VA SMALL | | | APPLIANCE CIRCUITS NOT 1 AS CALCULATED. FBC RERS E | | | 3703.2 | | | 4. LABEL GDO TO BE GFCI PROTECTED ON FLOOR PLAN. FBC | | | RES E3902.2 | | | 4.FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|