Plan Review Notes
Plan Review Notes For Permit 16020862
Permit Number 16020862
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-08 15:57:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROPOSED STRUCTURE IS LOCATED WITHIN 600 FEET OF
 A LARGE LAKE THAT IS AN EXPOSURE D CONDITION.
 THEREFORE, THE STRUCTURE IS REQUIRED TO BE DESIGNED FOR
 EXPOSURE D. FBC-R 301.2.1.4.3
  
 2) THE ENERGY COMPLIANCE FORMS CONTAINS ERRORS. THE
 DESIGN LOCATION IS WEST PALM BEACH, NOT BELLE GLADE.
 THE PLANS SPECIFY R-5 INSULATION ON THE EXTERIOR
 CONCRETE BLOCK WALLS AND THE FORM HAS R-30. THE OWNER'S
 OR AGENTS SIGNATURE IS REQUIRED ON THE FORM NOT THE
 NAME OF THEIR COMPANY. THE WALL BETWEEN THE LIVING
 SPACE AND THE GARAGE, THE ADJACENT WALL, IS NOT LISTED
 ON THE ENERGY COMPLIANCE FORM. THE PLAN SPECIFIES R-11
 IN THE ADJACENT WALL AND R-13 IS REQUIRED BY SECTION
 R402.1.1 OF THE ENERGY CODE.
  
 3) THE PRODUCT APPROVAL FOR THE SECTIONAL GARAGE DOOR
 IS FOR THE 2010 CODE VERSION. THE 2014 FLORIDA BUILDING
 CODE APPLIES TO THIS PROJECT.
  
 4) THE DESIGN LOAD PRESSURES LISTED IN THE PRODUCT
 APPROVAL FOR THE SECTIONAL GARAGE DOOR ARE NOT
 ADEQUATE, BASED ON THE OPENING PRESSURES SPECIFIED ON
 THE PLANS. FBC-R 301.1
  
 5) THE DESIGN LOAD PRESSURES LISTED IN THE PRODUCT
 APPROVAL FOR THE DOUBLE OUTSWING FRONT ENTRY DOOR ARE
 NOT ADEQUATE, BASED ON THE OPENING PRESSURES SPECIFIED
 ON THE PLANS. FBC-R 301.1
  
  
  
  
  
  
  
  
  
2016-03-28 13:15:52OPENED IN ERROR.