| 2016-02-25 07:22:34 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16020846 |
| | 2/25/16 |
| | |
| | 1) THE SUBMITTED ENERGY CONSERVATION FORM R402-2014 IS |
| | NOT FILLED OUT COMPLETELY. PLEASE REVIEW THE "SCOPE" |
| | SHOWN AT THE TOP OF THE FORM: "TO COMPLY, A BUILDING |
| | MUST MEET OR EXCEED ALL OF THE ENERGY EFFICIENCY |
| | REQUIREMENTS ON TABLE R402A AND ALL APPLICABLE |
| | MANDATORY REQUIREMENTS SUMMARIZED IN TABLE R402B OF |
| | THIS FORM". PLEASE ALSO SEE SECTION R101.4.5: CHANGE IN |
| | SPACE CONDITIONING. ANY NONCONDITIONED SPACE THAT IS |
| | ALTERED TO BECOME CONDITIONED SPACE SHALL BE REQUIRED |
| | TO BE BROUGHT INTO FULL COMPLIANCE WITH THIS CODE. |
| | PLEASE COMPLETE THE FORM AND RE-SUBMIT. |
| | 2) THE HVAC LOAD CALCULATIONS FORM MUST BE SIGNED BY |
| | THE PERSON WHO PERFORMED THE CALCULATIONS. |
| | 3) PLEASE INCLUDE THE R-VALUE OF THE FLEX DUCTS ON THE |
| | PLAN. |
| | 4) THE PLAN DOES NOT CLEARLY SHOW HOW THE RETURN AIR |
| | SYSTEM IS FUNCTIONING. IS THE AIR HANDLER INSTALLED |
| | VERTICALLY IN A CLOSET BEHIND A LOUVERED DOOR, OR IS IT |
| | IN THE ATTIC SPACE WITH A RETURN GRILL IN THE CEILING? |
| | PLEASE NOTE THAT AIR HANDLERS SHALL NOT BE INSTALLED IN |
| | THE ATTIC WHEN A HOME IS BROUGHT INTO COMPLIANCE USING |
| | R402- SEE SECTION R403.2.4 FBC-14 ENERGY CONSERVATION. |
| | 5) PROVIDE A CONDENSATE DISPOSAL PLAN. |
| | 6) THE PLAN HAS BEEN FORWARDED TO ELECTRICAL FOR |
| | REVIEW. |
| | |