| Plan Review Notes For Permit 16020831 |
| Permit Number |
16020831 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-09 11:26:58 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. SHEET A1- PLEASE UPDATE ALL REFERENCES TO REFLECT | | | CURRENT BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH | | | EDITION FAMILY, NEC 2011. | | | 2. PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS | | | ACCORDINGLY. LABEL NEW OR EXISTING FOR EXAMPLE | | | ELECTRICAL SERVICE MAIN AND INTERIOR DEVICES. FBC | | | 107.3.5 | | | 3. IF ELECTRICAL SERVICE IS NEW PROVIDE AIC CALCULATION | | | AND AIC RATING OF SERVICE EQUIPMENT. FBC RES E3606.3 | | | AND E3606.4 | | | 4. PROVIDE MANUF. CUT SHEETS FOR TANKLESS WATER HEATER | | | SHOWN. FBC 107.3.5 | | | 5. PANEL SCHEDULE TO COMPLY WITH FBC RES E3706.2- ID | | | CIRCUITS TO SHOW SPECIFIC PURPOSE OF USE. GENERAL | | | LIGHTING DESIGNATION WILL NOT SUFFICE. | | | 6. PROVIDE A NOTE TO COMPLY WITH THE FBC EC | | | CODE-R404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS. | | | 7. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL | | | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|