| Plan Review Notes For Permit 16020795 |
| Permit Number |
16020795 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-23 06:10:33 | 1) PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THEY CAN BE | | | CHANGED. SUBMIT PLANS IN AN UNERASABLE FORMAT. FBC SEC. | | | 107.2.1. | | | 2) THE WASHING MACHINE CANNOT BE INSTALLED ON A WET | | | VENT PER 2014 FPC SEC. 912.1. THE WASHING MACHINE SHALL | | | CONNECT TO THE HORIZONTAL DRAIN DOWNSTREAM OF THE | | | SHOWER. | | | 3) A CLEANOUT IS REQD. IN THE BASE OF THE WASHING | | | MACHINE STACK PER FPC SEC.708.3.4. | | | 4) THE DARK FLOOR PLAN THAT WAS SUBMITTED MAKES IT | | | DIFFICULT TO SEE THE CHANGES BEING MADE.TWO COPIES OF A | | | HAND DRAWN FLOOR PLAN SHOWING THE CHANGES WILL SUFFICE. | | | 5) THE PERMIT APPLICATION NOTES THE INSTALLATION OF 2 | | | SHOWER PANS BUT THE PLAN SHOWS A TUB AND A SHOWER. IS | | | THE TUB BEING CHANGED TO A SHOWER? INDICATE ON THE | | | APPLICATION AND THE NEW FLOOR PLAN. IF THE TUB IS BEING | | | REMOVED A SEPARATE PERMIT WILL BE REQUIRED BY A | | | CONTRACTOR FOR THE WALL REPAIR FOR THE TUB AND ALSO FOR | | | THE OTHER SHOWER. | | | 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE ELECTRIC | | | FOR THE TANKLESS WATER HEATER.SUBMIT TWO COPIES OF THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER | | | HEATER.FBC 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|