Plan Review Notes
Plan Review Notes For Permit 16020795
Permit Number 16020795
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-23 06:10:331) PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THEY CAN BE
 CHANGED. SUBMIT PLANS IN AN UNERASABLE FORMAT. FBC SEC.
 107.2.1.
 2) THE WASHING MACHINE CANNOT BE INSTALLED ON A WET
 VENT PER 2014 FPC SEC. 912.1. THE WASHING MACHINE SHALL
 CONNECT TO THE HORIZONTAL DRAIN DOWNSTREAM OF THE
 SHOWER.
 3) A CLEANOUT IS REQD. IN THE BASE OF THE WASHING
 MACHINE STACK PER FPC SEC.708.3.4.
 4) THE DARK FLOOR PLAN THAT WAS SUBMITTED MAKES IT
 DIFFICULT TO SEE THE CHANGES BEING MADE.TWO COPIES OF A
 HAND DRAWN FLOOR PLAN SHOWING THE CHANGES WILL SUFFICE.
 5) THE PERMIT APPLICATION NOTES THE INSTALLATION OF 2
 SHOWER PANS BUT THE PLAN SHOWS A TUB AND A SHOWER. IS
 THE TUB BEING CHANGED TO A SHOWER? INDICATE ON THE
 APPLICATION AND THE NEW FLOOR PLAN. IF THE TUB IS BEING
 REMOVED A SEPARATE PERMIT WILL BE REQUIRED BY A
 CONTRACTOR FOR THE WALL REPAIR FOR THE TUB AND ALSO FOR
 THE OTHER SHOWER.
 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE ELECTRIC
 FOR THE TANKLESS WATER HEATER.SUBMIT TWO COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER
 HEATER.FBC 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  