| Notes |
| Date |
Text |
| 2016-02-23 12:40:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A RESUME OF EXPERIENCE FOR THE | | | SHORING/RESHORE ENGINEER, FBC 110.3.5, 110.3.7.2. THIS | | | MAY BE SUBMITTED VIA EMAIL TO [email protected] AND | | | [email protected]. | | | | | | 2. THE LEVELS 2-8 SHORING CALCULATIONS PROVIDED IS A | | | DIGITALLY SIGNED DOCUMENT, WHICH IS NOT VALID AS A | | | PAPER SUBMITTAL. PROVIDE SIGNED, SEALED, DATED | | | ORIGINALS, FS471. | | | | | | 3. THE SHORING DRAWINGS ARE REQUIRED TO BE SIGNED, | | | SEALED, DATED ORIGINALS, FS471. | | | | | | 4. THE CONCRETE SHOPS WERE REVIEWED BY ONM&J, INITIALS | | | OF EJP AND B.GREENE, PERKINS EASTMAN. IF THE INDIVIDUAL | | | REVIEWING SHOP DRAWINGS OR DELEGATED ENGINEERING IS NOT | | | THE DESIGNER OF RECORD, PLEASE PROVIDE THE FULL NAME OF | | | THE INDIVIDUAL ON THE REVIEW STAMP AND THAT | | | INDIVIDUAL'S PE OR AR LICENSE NUMBER, FBC 107, FS471, | | | FS481. | | | | | | 5. PER KEN CONRAD, CHIEF BUILDING INSPECTOR, SUBMIT THE | | | GUARDRAIL SYSTEM DETAILS (PREPARED BY A DESIGN | | | PROFESSIONAL) FOR REVIEW. | | | |
|