Plan Review Notes
Plan Review Notes For Permit 16020761
Permit Number 16020761
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-22 07:07:55INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS AND
 GROUNDING ELECTRODE CONDUCTOR. NEC 310.15B16 AND NEC
 250.66.
 2. LABEL MAINS AS 1 OF 3, 2 OF 3, 3 OF 3 NEC 230.70
 3. SHOW TO PROVIDE AN INTERSYSTEM BONDING TERMINAL NEC
 250.94
 4. VERIFY IF THERE ARE EXISTING SMOKE DETECTORS, IF NOT
 SHOW AND PROVIDE PER FBC RES 314 REQUIREMENTS.
 5. FEEL FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  