| 2016-03-30 16:09:56 | PLUMBING COMMENTS: | | | | | | 1. TOILET PAPER DISPENSER IS TO BE MEASURED TO | | | CENTERLINE OF DISPENSER .PER FBC ACC. SEC. 604.7 | | | | | | 2. ACCESSIBLE TOILETS ARE TO BE MEASURED CENTER TO SIDE | | | WALL 16" MIN. TO 18" MAX. PER FRBC ACC. SEC. 604.2 | | | | | | 3. SHT. A802 ACCESSIBLE TOILET ROOMS FOR 139-140 SHOWS | | | THE LAV ENCROACHING ON THE 60:X59 CLEAR FLOOR SPACE FOR | | | TOILET IT SHALL COMPLY WITH FBC ACC SEC. 604.8.1.1 | | | | | | 4. SHT.A 902 WALLS AND PARTITIONS WITHIN 2 FEET OF | | | SERVICE SINKS,URINALS, AND WATER CLOSETS SHALL HAVE A | | | SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF NOT | | | LESS THAN FOUR FEET ABOVE THE FLOOR PER FBC SEC.604.2 | | | SECOND REQUEST | | | | | | 5. SUBMIT MANUFACTURERS SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE ROOF PIPING SUPPORTS BY MIRO | | | INDUSTRIES AND THE MIAMI DADE APPROVAL FOR THE TAM- PRO | | | 801 ROOF CEMENT. PER WPB AMEND. TO FBC 107.2.1.3 SECOND | | | REQUEST | | | | | | 6. SHT. P5.1 THE SANITARY RISER FOR ROOM #140 FOR THE | | | WATER CLOSET THE BANK OF LAVATORIES AND MOP SINK DOES | | | NOT COMPLY WITH FBC PL SEC.912 THE WATER CLOSET NEEDS | | | TO BE INDIVIDUALLY VENTED TOO COMPLY. | | | | | | | | | 2ND REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|