Plan Review Notes
Plan Review Notes For Permit 16020738
Permit Number 16020738
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-30 16:09:56PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSER IS TO BE MEASURED TO
 CENTERLINE OF DISPENSER .PER FBC ACC. SEC. 604.7
  
 2. ACCESSIBLE TOILETS ARE TO BE MEASURED CENTER TO SIDE
 WALL 16" MIN. TO 18" MAX. PER FRBC ACC. SEC. 604.2
  
 3. SHT. A802 ACCESSIBLE TOILET ROOMS FOR 139-140 SHOWS
 THE LAV ENCROACHING ON THE 60:X59 CLEAR FLOOR SPACE FOR
 TOILET IT SHALL COMPLY WITH FBC ACC SEC. 604.8.1.1
  
 4. SHT.A 902 WALLS AND PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS,URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN FOUR FEET ABOVE THE FLOOR PER FBC SEC.604.2
 SECOND REQUEST
  
 5. SUBMIT MANUFACTURERS SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE ROOF PIPING SUPPORTS BY MIRO
 INDUSTRIES AND THE MIAMI DADE APPROVAL FOR THE TAM- PRO
 801 ROOF CEMENT. PER WPB AMEND. TO FBC 107.2.1.3 SECOND
 REQUEST
  
 6. SHT. P5.1 THE SANITARY RISER FOR ROOM #140 FOR THE
 WATER CLOSET THE BANK OF LAVATORIES AND MOP SINK DOES
 NOT COMPLY WITH FBC PL SEC.912 THE WATER CLOSET NEEDS
 TO BE INDIVIDUALLY VENTED TOO COMPLY.
  
  
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  