| Plan Review Notes For Permit 16020738 |
| Permit Number |
16020738 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-22 14:44:49 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020738 | | | 3/22/16 | | | | | | SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I | | | HAVE REPRINTED THEM BELOW WITH SOME MODIFCATIONS: | | | | | | 2) M2.1: IT APPEARS THAT MAIN DUCT DROP SYMBOLS ARE | | | MISSING FOR RTU'S 1 & 6. | | | 3) M2.2: RTU-2 IS MISLABELED AS RTU-5. | | | 4) M2.2: THE PLAN SHEET IS MISLABELED AS "2ND FLOOR | | | DOMESTIC WATER PLAN". | | | 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE | | | RTU'S, EXHAUST FANS, AND THE CURBS- SEE STRUCTURAL | | | COMMENTS AND SECTION 301.15 FBC-10 MECHANICAL. | | | 7) INDICATE IF A ROOF LADDER OR OTHER MEANS IS EXISTING | | | FOR ACCESS TO THE ROOF TOP EQUIPMENT- SECTION 306.5. | | | 8) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A INTAKES- | | | SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | | 9) REFER TO SECTION C408 FBC-14 ENERGY CONSERVATION: | | | COMMISSIONING OF THE MECHANICAL AND ELECTRICAL POWER | | | AND LIGHTING SYSTEMS IS REQUIRED. PLEASE REVIEW ALL | | | SUB-SECTIONS AND SUBMIT A COMMISSIONING PLAN PER | | | SECTION C408.2.1. | | | 10) THERE ARE 11 AC SYSTEMS SHOWN ON THE PLANS | | | EXCLUDING THE EXISTING SYSTEM, HOWEVER THERE ARE ONLY | | | 10 SYSTEMS ACCOUNTED FOR IN THE ENERGY CONSERVATION | | | FORM, AND MANY OF THE BTUH CAPACITIES FOR THE SYSTEMS | | | LISTED IN THE CALCS DON'T MATCH THE CAPACITIES OF | | | LISTED IN THE SCHEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|