Plan Review Notes
Plan Review Notes For Permit 16020738
Permit Number 16020738
Review Stop B
Sequence Number 2
Notes
Date Text
2016-03-23 09:03:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020738
 ADD: 501 VILLAGE BLVD.
 CONT: MDS BUILDERS
 TEL: 561-241-8990
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 23/2016
 ACTION: DENIED
  
 1) SHEET 014_1544-A250 GROUND FLOOR LIFE SAFETY PLAN &
 009_2544-A201 GROUND FLOOR:
  
 1A) COMPLIED. LEVEL OF ALTERATION.
  
 1B) 2ND REQUEST. THE ENGINEER OF RECORD UNDER THE
 COMMENT (1A) WAS TO DETERMINE IF THIS RENOVATION WAS A
 LIMITED STRUCTURAL RENOVATION (LEVEL III LIMITED
 ALTERATION) OR LEVEL III SUBSTANTIAL STRUCTURAL
 ALTERATION REQUIRING THE ENGINEERING EVALUATION AND
 ANALYSIS TO BE COMPLETED OF THE STRUCTURAL FRAMEWORK OF
 THE BUILDING. THE SHEER WORK AREA OF THE 2 FLOORS AND
 ROOF AREA PUT THE LEVEL OF WORK AT 66% OF THE COMBINED
 SQUARE FOOTAGE OF THE 2 FLOORS AND ROOF AREA COMBINED,
 THE QUESTION IS? IS THERE OVER 30 % OF THE TOTAL SQUARE
 FOOTAGE OF THE COMBINED 2 FLOORS AND ROOF AREA OF
 STRUCTURAL ALTERATION? IF NOT THEN THE ALTERATION IS A
 LEVEL III LIMITED. THE LETTER WRITTEN BY JOEL
 MIDDLEBROOKES JR. P.E. PUTS THE ALTERATION AT A
 ALTERATION LEVEL II. PLEASE ALSO NOTE THIS IS A CHANGE
 OF OCCUPANCY AS WELL.
 ORIGINAL COMMENT: 1A) THE PROJECT DATA INDICATES
 ALTERATION LEVEL PER THE EXISTING BUILDING CODE
 CHAPTER 4 LEVEL III. PLEASE INDICATE IF THE ALTERATION
 LEVEL III IS CONSIDERED LIMITED (EXIST. BLDG. CODE
 907.4.3) OR SUBSTANTIAL PER (EXIST. BLDG. CODE
 907.4.2.).
  
 ORIGINAL COMMENT:1B) SHOW COMPLIANCE WITH THE 2014
 EXIST. BLDG. CODE 907.4.1 EVALUATION AND
 ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT
 ESTABLISHES THE STRUCTURAL ADEQUACY OF THE
 ALTERED STRUCTURE SHALL BE PREPARED BY A REGISTERED
 DESIGN PROFESSIONAL AND SUBMITTED TO THE CODE
 OFFICIAL.
  
 1C-G) COMPLIED.
  
 1H) BUILDING PROVISO: THE PLANS SHOW THE OFFICE LABELED
 121 A RAISED FLOOR AREA FROM THE REMAINDER OF THE REST
 OF THE FLOOR. 2014 FBC-ACCESS. CODE 201.1.1 VERTICAL
 ACCESSIBILITY EXCEPTION (3). OCCUPIABLE SPACES AND
 ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND THAT HOUSE NO
 MORE THAN FIVE PERSONS, INCLUDING, BUT NOT LIMITED TO
 EQUIPMENT CONTROL ROOMS AND PROJECTION BOOTHS.
 ADVISORY: . ALL NEW AND ALTERED AREAS MUST COMPLY WITH
 THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS. OWNER
 LEAVES THEMSELVES OPEN FOR A ADA LAWSUIT, NOT THROUGH
 THE FLORIDA ACCESSIBILITY CODE!!!!!!!!!!!
  
 1I-1L) COMPLIED
  
 1M) PROVISO: 2ND REQUEST. RESPONSE INDICATES HANDRAILS
 WERE ADDED TO THE RAMP THAT ACCESSES WORK ROOM #3 ON
 SHEETS A201 & A250. SHEET A201 IS CLOUDED BUT NO
 HANDRAILS WORK ROOM AREA # 3 IS RECEDED LOWER THAN THE
 MAIN FLOOR. THE PLANS INDICATE THE USE OF A RAMP TO
 GAIN ENTRY TO THIS WORK AREA. THE PLANS DO NOT INDICATE
 HANDRAILS ALONG THE RAMP AND COMPLIANCE WITH THE 2014
 FBC-ACCESS. 505.2 505.2 WHERE REQUIRED. HANDRAILS SHALL
 BE PROVIDED ON BOTH SIDES OF STAIRS AND RAMPS.
  
 1N) PROVISO: WORK AREA # 3 STAIRS LEADING TO THE
 EXTERIOR, THE DETAIL 5/A804 THE HANDRAIL/ GUARDRAIL
 SYSTEM. THE BOTTOM RETURN OF THE HORIZONTAL HANDRAIL
 EXTENSION (THE BOTTOM) CAN BE NO HIGHER THAN 27 INCHES
 ABOVE FINISH FLOOR TO COMPLY WITH 2014
 FBC-ACCESSIBILITY CODE 307.4.
  
 1O) COMPLIED.
  
 2) SHEET010_1544-A-202 SECOND FLOOR PLAN &
 015_1544-A251 THE SECOND FLOOR LIFE SAFETY PLAN:
  
 2A-D) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED. THE SUBMITTED WINDOW AND DOOR PRODUCT
 APPROVALS MEET THE REQUIRED PRESSURES;
 BLACK MOUNTAIN DOORS NOA 12-0323.04 8080 HMD-1L
 LOUVERED DOOR ?LMI
 E.S. WINDOWS SERIES 9000 OUTSWING FRENCH DOORS NOA
 13-0617.29-LMI
 E.S. WINDOWS SERIES 8000 ALUMINUM WINDOW WALL SYSTEM
 15-0727.05- LMI
 5) ROOFING SUBMITTAL JOHNS MANVILLE JM TPO SINGLE PLY
 ROOFING OVER STEEL DECK NOA 14-0618.04.
  
 5A) COMPLIED. REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5B) 2ND REQUEST . JOHNS MANVILLE JM TPO SINGLE PLY
 ROOFING OVER STEEL DECK NOA 14-0618.04. PLEASE NOTE
 NONE OF THE SUB-SYSTEMS WERE IDENTIFIED AS TO WHICH
 DECK WAS GOING TO BE APPLIED. REVIEW FASTENING PATTERNS
 MAXIMUM DESIGN PRESSURES ALLOWABLE AND IF GENERAL
 LIMITATION 7 OR 9. IF THE SUB-SYSTEM SELECTED INDICATES
 LIMITATION # 7 THEN A FLORIDA P.E. CAN CALCULATED THE
 RAS 117 CALCULATIONS FOR ROOF ZONE 2 (FLAT ROOF). THE
 STRUCTURAL SHEET 037_16029_ S3.0 HAS PRESSURES ONLY FOR
 THE FLAT DECK.
  
 6) PLEASE NOTE THE MECHANICAL SHEET 044_M7.1:
  
 6A) 2ND REQUEST. THE RESPONSE , SEE ATTACHED ANCHORAGE
 DETAIL BY STRUCTURAL ENGINEER. I DON?T SEE ANY
 ATTACHMENTS TO THE COMMENTS. THERE ARE NO OTHER LETTERS
 IN THE FOLDER FOR DOCUMENTS?
 THE ROOF MOUNTED EXHAUST FAN DETAIL DOES INDICATE THE
 ANCHORING AT 18 INCHES ON CENTER OR AS RECOMMENDED BY
 THE STRUCTURAL ENGINEER. NOTE ABOVE THE DETAIL IS FOR
 REFERENCE ONLY. TO BE VERIFIED BY A LICENSED STRUCTURAL
 ENGINEER. 2014 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 6B) 2ND REQUEST. THE RESPONSE , SEE ATTACHED DETAIL BY
 STRUCTURAL ENGINEER. I DON?T SEE ANY ATTACHMENTS TO THE
 COMMENTS. THERE ARE NO OTHER LETTERS IN THE FOLDER FOR
 DOCUMENTS?
 THE MECHANICAL PLAN PROVIDES A ROOF TOP CURB DETAIL.
 THE SAME NOTE APPLIES, . NOTE ABOVE THE DETAIL IS FOR
 REFERENCE ONLY. TO BE VERIFIED BY A LICENSED STRUCTURAL
 ENGINEER. 2014 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 7) 2ND REQUEST. THE RESPONSE , SEE ATTACHED DETAIL BY
 STRUCTURAL ENGINEER. I DON?T SEE ANY ATTACHMENTS TO THE
 COMMENTS. THERE ARE NO OTHER LETTERS IN THE FOLDER FOR
 DOCUMENTS?
 THE PLANS ARE SILENT ALSO HOW THE NEW RTU UNITS ARE
 GOING TO BE ATTACHED TO THE ROOF TOP CURBS. 2014 FBC-M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  