| 2016-03-08 05:33:57 | 1) PROVIDE THE INSIDE CLEAR DIMWNSIONS OF THE |
| | ACCESSIBLE TOILET COMPARTMENTS IN ROOMS # 139 & 140 AND |
| | 204 & 205. THE MINIMUM WIDTH SHALL BE 85 INCHES. 86 |
| | INCHES ALLOWS FOR TOLERANCE. COMPLY WITH FAC SEC. |
| | 604.8.1. |
| | 2) AT LEAST ONE AMBULATORY STALL COMPLYING WITH 2014 |
| | FL. ACCESSIBILITY CODE SEC.604.8.2 IS REQUIRED WHERE |
| | SIX OR MORE TOILET COMPARTMENTS ARE PROVIDED, OR WHERE |
| | THE COMBINATION OF URINALS AND WATER CLOSETS TOTALS SIX |
| | OR MORE FIXTURES. FAC SEC. 213.3.1. SEE ROOMS #139 & |
| | 140 AND ROOM #204. |
| | 3) THE HI SIDE DRINKING FOUNTAIN IN ROOM #115 SHALL |
| | COMPLY WITH FAC SEC.307.2. AN OPTIONAL SKIRT MAY BE |
| | REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES, |
| | 4) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET |
| | RROOMS AND TOILET COMPARTMENTS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE 2014 FAC SEC.604.7. |
| | 5) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER THE FAC SEC. 609.4. SHOW THIS ON |
| | THE MOUNTING HEIGHT DETAILS. |
| | 6) SHTS. A801, 802, & 803 SHOW THE CENTERLINE OF THE |
| | WATER CLOSET AS 20 INCHES FROM THE ADJACENT WALL. THE |
| | WATER CLOSET SHALL BE LOCATED 16"-18" FROM THE ADJACENT |
| | WALL. 2014 FAC SEC.604.2. |
| | 7) SHT. A 902 - WALLS AND PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN FOUR FEET ABOVE THE FLOOR PER 2014 FBC |
| | SEC.1210.2.2. |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE ROOF PIPING SUPPORTS |
| | BY MIRO INDUSTRIES AND THE MIAMI - DADE APPROVAL FOR |
| | THE TAM-PRO 801 ROOF CEMENT . |
| | 9) SHT. P5.1 - THE SANITARY RISER FOR ROOM #140 FOR THE |
| | WATER CLOSET AND BANK OF LAVATORIES DOES NOT COMPLY |
| | WITH 2014 FPC SEC.912 FOR A HORIZONTAL WET VENT. |
| | INDIVIDUALLY VENTING WATER CLOSET WC-2 WILL SOLVE THIS |
| | ISSUE. |
| | 10) SHT. P5.1 - THE SANITARY RISER FOR TOILET ROOMS |
| | #139 & #140 DOES NOT COMPLY WITH 2014 FPC SEC.914 FOR A |
| | CIRCUIT VENT. |
| | 11) SHT. P5.1.THE SECOND FLOOR SANITARY PLAN VIEW |
| | DRAWING DOES NOT CORRELATE WITH THE RISER. REFER TO THE |
| | LAVATORIES IN THE WOMEN'S RESTROOM. |
| | |