Plan Review Notes
Plan Review Notes For Permit 16020738
Permit Number 16020738
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-08 05:33:571) PROVIDE THE INSIDE CLEAR DIMWNSIONS OF THE
 ACCESSIBLE TOILET COMPARTMENTS IN ROOMS # 139 & 140 AND
 204 & 205. THE MINIMUM WIDTH SHALL BE 85 INCHES. 86
 INCHES ALLOWS FOR TOLERANCE. COMPLY WITH FAC SEC.
 604.8.1.
 2) AT LEAST ONE AMBULATORY STALL COMPLYING WITH 2014
 FL. ACCESSIBILITY CODE SEC.604.8.2 IS REQUIRED WHERE
 SIX OR MORE TOILET COMPARTMENTS ARE PROVIDED, OR WHERE
 THE COMBINATION OF URINALS AND WATER CLOSETS TOTALS SIX
 OR MORE FIXTURES. FAC SEC. 213.3.1. SEE ROOMS #139 &
 140 AND ROOM #204.
 3) THE HI SIDE DRINKING FOUNTAIN IN ROOM #115 SHALL
 COMPLY WITH FAC SEC.307.2. AN OPTIONAL SKIRT MAY BE
 REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES,
 4) TOILET PAPER DISPENSERS IN THE ACCESSIBLE TOILET
 RROOMS AND TOILET COMPARTMENTS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE 2014 FAC SEC.604.7.
 5) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE FAC SEC. 609.4. SHOW THIS ON
 THE MOUNTING HEIGHT DETAILS.
 6) SHTS. A801, 802, & 803 SHOW THE CENTERLINE OF THE
 WATER CLOSET AS 20 INCHES FROM THE ADJACENT WALL. THE
 WATER CLOSET SHALL BE LOCATED 16"-18" FROM THE ADJACENT
 WALL. 2014 FAC SEC.604.2.
 7) SHT. A 902 - WALLS AND PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN FOUR FEET ABOVE THE FLOOR PER 2014 FBC
 SEC.1210.2.2.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE ROOF PIPING SUPPORTS
 BY MIRO INDUSTRIES AND THE MIAMI - DADE APPROVAL FOR
 THE TAM-PRO 801 ROOF CEMENT .
 9) SHT. P5.1 - THE SANITARY RISER FOR ROOM #140 FOR THE
 WATER CLOSET AND BANK OF LAVATORIES DOES NOT COMPLY
 WITH 2014 FPC SEC.912 FOR A HORIZONTAL WET VENT.
 INDIVIDUALLY VENTING WATER CLOSET WC-2 WILL SOLVE THIS
 ISSUE.
 10) SHT. P5.1 - THE SANITARY RISER FOR TOILET ROOMS
 #139 & #140 DOES NOT COMPLY WITH 2014 FPC SEC.914 FOR A
 CIRCUIT VENT.
 11) SHT. P5.1.THE SECOND FLOOR SANITARY PLAN VIEW
 DRAWING DOES NOT CORRELATE WITH THE RISER. REFER TO THE
 LAVATORIES IN THE WOMEN'S RESTROOM.
  
 PLUMBING PLAN REVIEW