2016-03-11 15:34:291ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020738
 3/11/16
  
 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S 1, 2, 3, 4, 7, 8, 9, 10, 11 PER
 SECTION 606.2.1. PROVIDE AN INSTALLATION DETAIL ON THE
 PLAN AND INDICATE HOW THE DEVICES WILL BE SUPERVISED-
 SECTION 606.4.1.
 2) M2.1: IT APPEARS THAT MAIN DUCT DROP SYMBOLS ARE
 MISSING FOR RTU'S 1 & 2.
 3) M2.2: RTU-2 IS MISLABELED AS RTU-5.
 4) M2.2: THE PLAN SHEET IS MISLABELED AS "2ND FLOOR
 DOMESTIC WATER PLAN".
 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL RTU'S, EXHAUST FANS, AND AIR INTAKE OPENINGS.
 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 RTU'S, EXHAUIST FANS, AND THE CURBS- SEE STRUCTURAL
 COMMENTS AND SECTION 301.15 FBC-10 MECHANICAL.
 7) INDICATE IF A ROOF LADDER OR OTHER MEANS IS EXISTING
 FOR ACCESS TO THE ROOF TOP EQUIPMENT- SECTION 306.5.
 8) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A INTAKES-
 SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION.
 9) REFER TO SECTION C408 FBC-14 ENERGY CONSERVATION:
 COMMISSIONING OF THE MECHANICAL AND ELECTRICAL POWER
 AND LIGHTING SYSTEMS IS REQUIRED. PLEASE REVIEW ALL
 SUB-SECTIONS AND SUBMIT A COMMISSIONING PLAN PER
 SECTION C408.2.1.
 10) THERE ARE 12 AC SYSTEMS SHOWN ON THE PLANS
 EXCLUDING THE EXISTING SYSTEM, HOWEVER THERE ARE ONLY
 10 SYSTEMS ACCOUNTED FOR IN THE ENERGY CONSERVATION
 FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER