2016-03-01 17:19:381ST ELECTRICAL REVIEW
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014
 2011 EDITION OF THE NEC
  
 CORRECTIONS REQUIRED:
 SHEET E2.1
 1. CONFERENCE ROOM 104 MISSING EMERGENCY LIGHTING.
 2. CORRIDOR BETWEEN MAIN WORK AREAS 1 & 2 REQUIRES
 LIGHTING.
 3. CONFERENCE ROOM 156 MISSING EMERGENCY LIGHTING.
 4. THIS CORRIDOR AREA IS UNDEFINED AND MAY REQUIRE
 EMERGENCY LIGHTING.
 5. KEY NOTE 1 REFERS TO SHEET E0.1 WHICH IS MISSING.
 LIGHTING DETAIL IS REQUIRED TO VERIFY COMPLIANCE WITH
 THE FBC-EC405.2.2.1 LIGHT REDUCTION (DIMMING) AND
 FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL.
 6. PER NEC 110.26(D) THE OCCUPANCY SENSOR IS PROHIBITED
 IN THE ELECTRIC EQUIPMENT ROOM. ELECTRIC ROOM 157
 7. THIS LABEL APPEARS TO BE FOR THE ELECTRIC ROOM. NO
 STORAGE ALLOWED IN ELECTRIC ROOM. RENAME THIS
 ACCORDINGLY. STG. 157
 8. SAME AS NOTE 6 ABOVE. ELECTRIC ROOM 109.
 9. SAME AS NOTE 6 ABOVE. MAIN ELECTRICAL ROOM
 10. SAME AS NOTES 6 & 7 ABOVE. STG. 130
 SHEET E2.2
 1. SEE NOTE 5: KEY NOTE 1 REFERS TO SHEET E0.1 WHICH IS
 MISSING. LIGHTING DETAIL IS REQUIRED TO VERIFY
 COMPLIANCE WITH THE FBC-EC405.2.2.1 LIGHT REDUCTION
 (DIMMING) AND FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL.
 2. CONFERENCE ROOM 219 MISSING EMERGENCY LIGHTING.
 3. CONFERENCE ROOM 224 MISSING EMERGENCY LIGHTING.
 4. STAIRWELL MISSING EMERGENCY LIGHTING.
 5. SEE NOTE 6 E2.1 PER NEC 110.26(D) THE OCCUPANCY
 SENSOR IS PROHIBITED IN THE ELECTRIC EQUIPMENT ROOM.
 ELECTRIC ROOM 212
 SHEET E3.1
 1. PER NEC 210.8(B)5 ALL RECEPTACLES WITHIN 6? OF THE
 SINK SHALL BE GFCI PROTECTED. BREAK ROOM
 2. PER NEC 210.8(B)5 ALL RECEPTACLES WITHIN 6? OF THE
 SINK SHALL BE GFCI PROTECTED. CAFETERIA/VENDING AREA.
 SHEET E3.3
 1. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 SHEET E6.1
 1. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
 2. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT
 DURABLY MARKED AND DATED ON ALL NON-DWELLING ELECTRICAL
 APPARATUS.
 3. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS
 SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY
 DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND
 TYPE OF THE SOURCE OF POWER.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  