| 2016-03-01 17:19:38 | 1ST ELECTRICAL REVIEW |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION OF THE FBC 2014 |
| | 2011 EDITION OF THE NEC |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET E2.1 |
| | 1. CONFERENCE ROOM 104 MISSING EMERGENCY LIGHTING. |
| | 2. CORRIDOR BETWEEN MAIN WORK AREAS 1 & 2 REQUIRES |
| | LIGHTING. |
| | 3. CONFERENCE ROOM 156 MISSING EMERGENCY LIGHTING. |
| | 4. THIS CORRIDOR AREA IS UNDEFINED AND MAY REQUIRE |
| | EMERGENCY LIGHTING. |
| | 5. KEY NOTE 1 REFERS TO SHEET E0.1 WHICH IS MISSING. |
| | LIGHTING DETAIL IS REQUIRED TO VERIFY COMPLIANCE WITH |
| | THE FBC-EC405.2.2.1 LIGHT REDUCTION (DIMMING) AND |
| | FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL. |
| | 6. PER NEC 110.26(D) THE OCCUPANCY SENSOR IS PROHIBITED |
| | IN THE ELECTRIC EQUIPMENT ROOM. ELECTRIC ROOM 157 |
| | 7. THIS LABEL APPEARS TO BE FOR THE ELECTRIC ROOM. NO |
| | STORAGE ALLOWED IN ELECTRIC ROOM. RENAME THIS |
| | ACCORDINGLY. STG. 157 |
| | 8. SAME AS NOTE 6 ABOVE. ELECTRIC ROOM 109. |
| | 9. SAME AS NOTE 6 ABOVE. MAIN ELECTRICAL ROOM |
| | 10. SAME AS NOTES 6 & 7 ABOVE. STG. 130 |
| | SHEET E2.2 |
| | 1. SEE NOTE 5: KEY NOTE 1 REFERS TO SHEET E0.1 WHICH IS |
| | MISSING. LIGHTING DETAIL IS REQUIRED TO VERIFY |
| | COMPLIANCE WITH THE FBC-EC405.2.2.1 LIGHT REDUCTION |
| | (DIMMING) AND FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL. |
| | 2. CONFERENCE ROOM 219 MISSING EMERGENCY LIGHTING. |
| | 3. CONFERENCE ROOM 224 MISSING EMERGENCY LIGHTING. |
| | 4. STAIRWELL MISSING EMERGENCY LIGHTING. |
| | 5. SEE NOTE 6 E2.1 PER NEC 110.26(D) THE OCCUPANCY |
| | SENSOR IS PROHIBITED IN THE ELECTRIC EQUIPMENT ROOM. |
| | ELECTRIC ROOM 212 |
| | SHEET E3.1 |
| | 1. PER NEC 210.8(B)5 ALL RECEPTACLES WITHIN 6? OF THE |
| | SINK SHALL BE GFCI PROTECTED. BREAK ROOM |
| | 2. PER NEC 210.8(B)5 ALL RECEPTACLES WITHIN 6? OF THE |
| | SINK SHALL BE GFCI PROTECTED. CAFETERIA/VENDING AREA. |
| | SHEET E3.3 |
| | 1. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | SHEET E6.1 |
| | 1. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | 2. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT |
| | DURABLY MARKED AND DATED ON ALL NON-DWELLING ELECTRICAL |
| | APPARATUS. |
| | 3. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS |
| | SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY |
| | DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND |
| | TYPE OF THE SOURCE OF POWER. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |