| 2016-03-02 16:13:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020738 |
| | ADD: 501 VILLAGE BLVD. |
| | CONT: MDS BUILDERS |
| | TEL: 561-241-8990 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 03/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 014_1544-A250 GROUND FLOOR LIFE SAFETY PLAN & |
| | 009_2544-A201 GROUND FLOOR: |
| | 1A) THE PROJECT DATA INDICATES ALTERATION LEVEL PER THE |
| | EXISTING BUILDING CODE CHAPTER 4 LEVEL III. PLEASE |
| | INDICATE IF THE ALTERATION LEVEL III IS CONSIDERED |
| | LIMITED (EXIST. BLDG. CODE 907.4.3) OR SUBSTANTIAL PER |
| | (EXIST. BLDG. CODE 907.4.2.). |
| | |
| | 1B) SHOW COMPLIANCE WITH THE 2014 EXIST. BLDG. CODE |
| | 907.4.1 EVALUATION AND ANALYSIS. AN ENGINEERING |
| | EVALUATION AND ANALYSIS THAT ESTABLISHES THE STRUCTURAL |
| | ADEQUACY OF THE ALTERED STRUCTURE SHALL BE PREPARED BY |
| | A REGISTERED DESIGN PROFESSIONAL AND SUBMITTED TO THE |
| | CODE OFFICIAL. |
| | |
| | 1C) THE VERTICAL EXIT NEXT TO THE EXTERIOR SERVICE YARD |
| | DOES NOT SHOW AN EXIT DOORWAY REQUIRED BY FBC-B 1027.1. |
| | |
| | 1D) THE EXTERIOR EQUIPMENT COURTYARD IS ALSO BEING USED |
| | AS PART OF THE EXIT DISCHARGE. THERE ARE 3 EXITS THAT |
| | EMPTY INTO THIS EQUIPMENT SERVICE YARD, THE VERTICAL |
| | EXIT, CONFERENCE ROOM # 10 AND PORTIONS OF THE OFFICE |
| | AREA. PLEASE PROVIDE AN EQUIPMENT LAYOUT OF THIS AREA |
| | WHERE A MINIMUM WIDTH OF 44 INCHES CAN BE MAINTAINED |
| | FOR SERVING THE EGRESS COURT. 2014 FBC-B 1027.1. |
| | |
| | 1E) VESTIBULE 137 LEADS INTO BOTH THE WOMEN?S RESTROOM |
| | 140 AND THE MEN?S RESTROOM 139. PLEASE SEE DOORS IN |
| | SERIES IN THE LADIES RESTROOM DOORS 135 & 140 IN THE |
| | MEN?S RESTROOM 138 & 139. PLEASE SHOW CODE COMPLIANCE |
| | WITH THE 2014 FBC-ACCESS. CODE 404.2.6. |
| | |
| | 1F) BOTH THE WOMEN?S RESTROOM 140 AND THE MEN?S |
| | RESTROOM 139 BOTH HAVE 6 OR MORE WATER CLOSETS OR |
| | COMBINATION OF WATER CLOSETS AND URINALS. PLEASE SHOW |
| | COMPLIANCE WITH; |
| | 2014 FBC-ACCESS. CODE 213.3.1 TOILET COMPARTMENTS. |
| | WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| | 604.8.2 (1-3) WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| | CLOSETS TOTALS SIX OR MORE FIXTURES. |
| | |
| | 1G) SHEET 009_1544-A201 SHOWS A DETAIL 3/A904 FOR THE |
| | USE OF ACCORDION DOORS SEPARATING THE CONFERENCE ROOM. |
| | THIS DETAIL INDICATES THE STRUCTURAL SUPPORT BY OTHERS. |
| | THE S1.1 SHEET SHOWS LINE OF PARTITION BEAM ABOVE BUT |
| | NO MENTION OF THE ADDITIONAL STRUCTURAL SUPPORT |
| | REQUIRED FOR THE FOLDING DOOR SYSTEM. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. THIS CAN BE IF |
| | REQUESTED A DEFERRED SUBMITTAL. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 1H) THE PLANS SHOW THE OFFICE LABELED 121 A RAISED |
| | FLOOR AREA FROM THE REMAINDER OF THE REST OF THE FLOOR. |
| | PLEASE SHOE COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE |
| | 201.1.1 VERTICAL ACCESSIBILITY. |
| | |
| | 1I) THE PLANS SHOW THE OFFICE LABELED 121 A RAISED |
| | FLOOR AREA FROM THE REMAINDER OF THE REST OF THE FLOOR. |
| | THE PLANS DO NOT SHOW HANDRAILS ON EITHER PAIRS OF |
| | STEPS, SHOW COMPLIANCE WITH THE 2014 EXIST. BLDG. CODE |
| | 805.9 HANDRAILS. THE REQUIREMENTS OF SECTIONS 805.9.1 |
| | AND 805.9.2 SHALL APPLY TO HANDRAILS FROM THE WORK AREA |
| | FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT DISCHARGE. |
| | |
| | 805.9.1 MINIMUM REQUIREMENT. EVERY REQUIRED EXIT |
| | STAIRWAY THAT IS PART OF THE MEANS OF EGRESS FOR ANY |
| | WORK AREA AND THAT HAS THREE OR MORE RISERS AND IS NOT |
| | PROVIDED WITH AT LEAST ONE HANDRAIL. |
| | |
| | 805.9.2 DESIGN. HANDRAILS REQUIRED IN ACCORDANCE WITH |
| | SECTION 805.9.1 SHALL BE DESIGNED AND INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2014 FBC ACCESS. CODE 505.10.2 TOP EXTENSIONS AT STAIRS |
| | AND 505.10.3 BOTTOM EXTENSIONS AT STAIRS. |
| | |
| | 1J) THE CAFETERIA/ VENDING AREA DOES NOT SHOW |
| | COMPLIANCE WITH: 2014 FBC- ACCESS. CODE 226.1 WHERE |
| | DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF |
| | FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES |
| | AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. |
| | |
| | 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | |
| | 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 1K) PLEASE SEE OFFICE DOOR 151 A INSWING DOOR AND ONLY |
| | 1FOOT ON THE LATCH SIDE OF THE DOOR. THE 2014 |
| | FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES WILL |
| | REQUIRE 18 INCHES SEE FIGURE 404.2.4.1(A). |
| | |
| | 1L) THE RECEPTION AREA 155 HAS A NOTE 13 THAT THE |
| | RECEPTION AREA IS PART OF THE OFFICE FURNITURE PACKAGE, |
| | PLEASE NOTE FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | |
| | 1M) WORK ROOM AREA # 3 IS RECEDED LOWER THAN THE MAIN |
| | FLOOR. THE PLANS INDICATE THE USE OF A RAMP TO GAIN |
| | ENTRY TO THIS WORK AREA. THE PLANS DO NOT INDICATE |
| | HANDRAILS ALONG THE RAMP AND COMPLIANCE WITH THE 2014 |
| | FBC-ACCESS. 505.2 505.2 WHERE REQUIRED. HANDRAILS SHALL |
| | BE PROVIDED ON BOTH SIDES OF STAIRS AND RAMPS. |
| | |
| | 1N) IN THE WORK AREA # 3 THERE ARE STAIRS TO THE |
| | EXTERIOR OF THE BUILDING PLEASE SHOW COMPLIANCE WITH |
| | THE 2014 EXIST. BLDG. CODE 805.9 HANDRAILS. THE |
| | REQUIREMENTS OF SECTIONS 805.9.1 AND 805.9.2 SHALL |
| | APPLY TO HANDRAILS FROM THE WORK AREA FLOOR TO, AND |
| | INCLUDING, THE LEVEL OF EXIT DISCHARGE. |
| | |
| | 805.9.1 MINIMUM REQUIREMENT. EVERY REQUIRED EXIT |
| | STAIRWAY THAT IS PART OF THE MEANS OF EGRESS FOR ANY |
| | WORK AREA AND THAT HAS THREE OR MORE RISERS AND IS NOT |
| | PROVIDED WITH AT LEAST ONE HANDRAIL. |
| | |
| | 805.9.2 DESIGN. HANDRAILS REQUIRED IN ACCORDANCE WITH |
| | SECTION 805.9.1 SHALL BE DESIGNED AND INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2014 FBC ACCESS. CODE 505.10.2 TOP EXTENSIONS AT STAIRS |
| | AND 505.10.3 BOTTOM EXTENSIONS AT STAIRS. |
| | |
| | 1O) NONE OF THE STAIRS SHOW COMPLIANCE WITH THE 2014 |
| | FBC-ACCESS. CODE 307.4 VERTICAL CLEARANCE, ALSO SEE |
| | FIGURE 307.4. |
| | |
| | 2) SHEET010_1544-A-202 SECOND FLOOR PLAN & |
| | 015_1544-A251 THE SECOND FLOOR LIFE SAFETY PLAN: |
| | 2A) IN THE MEN?S RESTROOM THERE IS A TOTAL OF COMBINED |
| | TOTAL OF 7 WATER CLOSETS AND URINALS, PLEASE SHOW |
| | COMPLIANCE WITH: |
| | 2014 FBC-ACCESS. CODE 213.3.1 TOILET COMPARTMENTS. |
| | WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| | 604.8.2 (1-3) WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| | CLOSETS TOTALS SIX OR MORE FIXTURES. |
| | |
| | 2B) DOOR 220 THERE IS ONLY 9 INCHES ON THE LATCH SIDE |
| | OF THE DOOR, PULL SIDE THE 2014 FBC-ACCESS. CODE |
| | 404.2.4.1(A) REQUIRES A MINIMUM OF 18 INCHES. |
| | |
| | 2C) DOOR 214 THERE IS ONLY APPROXIMATELY 1 FOOT INCHES |
| | ON THE LATCH SIDE OF THE DOOR, PULL SIDE THE 2014 |
| | FBC-ACCESS. CODE 404.2.4.1(A) REQUIRES A MINIMUM OF 18 |
| | INCHES. |
| | |
| | 2D) CATWALK 213 HAS A NOTE # 23. A 5 FOOT WIDE X 3 FOOT |
| | 4 INCH HIGH CASED OPENING IN NEW DRYWALL PARTITION. |
| | MATCH HEAD AND SILL HEIGHT ON THE OPPOSITE SIDE OF THE |
| | CATWALK. THE PLANS DO NOT INDICATE THE ACTUAL HEIGHT |
| | FROM THE FINISH FLOOR. IF A GUARDRAIL SYSTEM OR PORTION |
| | OF THE OPENING NEED TO PROVIDE PROTECTION IN COMPLIANCE |
| | WITH: |
| | FBC-B 1013.4 OPENING LIMITATIONS. REQUIRED GUARDS SHALL |
| | NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE 4 |
| | INCHES (102 MM) IN DIAMETER FROM THE WALKING SURFACE TO |
| | THE REQUIRED GUARD HEIGHT. |
| | |
| | 3) IN THE ABOVE COMMENTS THERE ARE A NUMBER OF |
| | ACCESSIBILITY CODE ISSUES. UNDER THE 2014 EXISTING |
| | BUILDING CODE LEVEL II AND LEVEL III BOTH REFER TO THE |
| | FLORIDA ACCESSIBILITY CODE. |
| | 2014 FBC-ACCESS. CODE 202.4.1 DISPROPORTIONATE COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. |
| | 20% PERCENT OF THE CONTRACT VALUE IS $480,000.00 TO BE |
| | SPENT IN MAKING ACCESSIBLE UPGRADES. PLEASE NOTE 202.4 |
| | DOES ALLOW YOU TO BACK OUT THE WINDOW AND DOOR PORTION |
| | OF THE CONTRACT VALUE AND IN DOING SO THE 20% IN |
| | ACCESSIBLE UPGRADES. |
| | |
| | PLEASE SEE THE ORDER OF WHAT TAKES PRIORITY IN |
| | ACCESSIBLE UPGRADES. |
| | FBC-ACCESS. CODE. 202.4.2 ACCESSIBLE FEATURES IN THE |
| | EVENT OF DISPROPORTIONALITY. WHEN THE COST OF |
| | ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE |
| | ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO |
| | THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL |
| | SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE |
| | MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE |
| | COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE |
| | ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE |
| | ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 4) THE SUBMITTED WINDOW AND DOOR PRODUCT APPROVALS MEET |
| | THE REQUIRED PRESSURES; |
| | BLACK MOUNTAIN DOORS NOA 12-0323.04 8080 HMD-1L |
| | LOUVERED DOOR ?LMI |
| | E.S. WINDOWS SERIES 9000 OUTSWING FRENCH DOORS NOA |
| | 13-0617.29-LMI |
| | E.S. WINDOWS SERIES 8000 ALUMINUM WINDOW WALL SYSTEM |
| | 15-0727.05- LMI |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) ROOFING SUBMITTAL JOHNS MANVILLE JM TPO SINGLE PLY |
| | ROOFING OVER STEEL DECK NOA 14-0618.04. |
| | |
| | 5A) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5B) JOHNS MANVILLE JM TPO SINGLE PLY ROOFING OVER STEEL |
| | DECK NOA 14-0618.04. PLEASE NOTE NONE OF THE |
| | SUB-SYSTEMS WERE IDENTIFIED AS TO WHICH DECK WAS GOING |
| | TO BE APPLIED. REVIEW FASTENING PATTERNS MAXIMUM DESIGN |
| | PRESSURES ALLOWABLE AND IF GENERAL LIMITATION 7 OR 9. |
| | IF THE SUB-SYSTEM SELECTED INDICATES LIMITATION # 7 |
| | THEN A FLORIDA P.E. CAN CALCULATED THE RAS 117 |
| | CALCULATIONS FOR ROOF ZONE 2 (FLAT ROOF). THE |
| | STRUCTURAL SHEET 037_16029_ S3.0 HAS PRESSURES ONLY FOR |
| | THE FLAT DECK. |
| | |
| | 6) PLEASE NOTE THE MECHANICAL SHEET 044_M7.1: |
| | |
| | 6A) THE ROOF MOUNTED EXHAUST FAN DETAIL DOES INDICATE |
| | THE ANCHORING AT 18 INCHES ON CENTER OR AS RECOMMENDED |
| | BY THE STRUCTURAL ENGINEER. NOTE ABOVE THE DETAIL IS |
| | FOR REFERENCE ONLY. TO BE VERIFIED BY A LICENSED |
| | STRUCTURAL ENGINEER. 2014 FBC-M- 301.15 WIND |
| | RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 6B) THE MECHANICAL PLAN PROVIDES A ROOF TOP CURB |
| | DETAIL. THE SAME NOTE APPLIES, . NOTE ABOVE THE DETAIL |
| | IS FOR REFERENCE ONLY. TO BE VERIFIED BY A LICENSED |
| | STRUCTURAL ENGINEER. 2014 FBC-M- 301.15 WIND |
| | RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 7) THE PLANS ARE SILENT ALSO HOW THE NEW RTU UNITS ARE |
| | GOING TO BE ATTACHED TO THE ROOF TOP CURBS. 2014 FBC-M- |
| | 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |