| Plan Review Notes For Permit 16020711 |
| Permit Number |
16020711 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-18 16:22:50 | 1ST REVIEW: FBC 2014 BUILDING | | | PERMIT #16020711 | | | 2/18/16 | | | | | | 1) THE PERMIT APPLICATION INDICATES "BUILD UP AND | | | SHINGLES RE-ROOF". PLEASE SUBMIT A VALID FL. PRODUCT | | | APPROVAL OR MIAMI-DADE NOA FOR THE ROOF SHINGLES. | | | 2) THE PRODUCT APPROVAL FOR THE GAF W-13 SYSTEM | | | SELECTED ON PAGE 6 INDICATES A MECHANICALLY FASTENED | | | BASE SHEET. PLEASE SEE NOTE 5.7 ON PAGE 4 OF 4: "ZONES | | | 2 AND 3 SHALL EMPLOY AN ATTACHMENT DENSITY DESIGNED BY | | | A QUALIFIED DESIGN PROFESSIONAL TO RESIST THE ELEVATED | | | PRESSURE DESIGN." PLEASE PROVIDE SUPPLEMENTAL | | | ENGINEERING AS REQUIRED. | | | 3) PLEASE PROVIDE A BASIC DIMENSIONED DIAGRAM THAT | | | CLEARLY ILLUSTRATES THE SLOPED AND FLAT AREAS OF THE | | | ROOF, AND ADJUST THE PERMIT APPLICATION TO INDICATE | | | SQUARE FOOTAGE AREAS OF BOTH SLOPED AND FLAT ROOFS. | | | | | | CHRISTOPHER L. COLE | | | STANDARDL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|