| 2016-02-25 12:39:14 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16020687 |
| | 2/25/16 |
| | |
| | 1) PLEASE REFER TO SECTION 404.1 AND PROVIDE MECHANICAL |
| | VENTILATION FOR THE GARAGE SHOWN ON THE PLAN AS |
| | STORAGE. |
| | |
| | 404.1 ENCLOSED PARKING GARAGES. |
| | MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING |
| | GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN |
| | ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH. |
| | 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR |
| | THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC |
| | DETECTION DEVICES. |
| | 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS |
| | APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS. |
| | SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | THEIR MANUFACTURERS? RECOMMENDATIONS. |
| | |
| | 404.2 MINIMUM VENTILATION. |
| | AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT REDUCE THE |
| | VENTILATION AIRFLOW RATE BELOW 0.05 CFM PER SQUARE FOOT |
| | (0.00025 M3/S ? M2) OF THE FLOOR AREA AND THE SYSTEM |
| | SHALL BE CAPABLE OF PRODUCING A VENTILATION AIRFLOW |
| | RATE OF 0.75 CFM PER SQUARE FOOT (0.0038 M3/S ? M2) OF |
| | FLOOR AREA. |
| | |
| | 404.3 OCCUPIED SPACES ACCESSORY TO PUBLIC GARAGES. |
| | CONNECTING OFFICES, WAITING ROOMS, TICKET BOOTHS AND |
| | SIMILAR USES THAT ARE ACCESSORY TO A PUBLIC GARAGE |
| | SHALL BE MAINTAINED AT A POSITIVE PRESSURE AND SHALL BE |
| | PROVIDED WITH VENTILATION IN ACCORDANCE WITH SECTION |
| | 403.3. |
| | |
| | 2) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA #12-0830.07 |
| | FOR THE OUTSIDE AIR LOUVERS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |