2016-03-15 14:17:23RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014)
  
 1- ARCHITECT OF RECORD TO REVISE THE DESIGN PRESSURES
 FOR DOORS AND WINDOWS. DESIGN PRESSURES SHOWN ON SHEET
 A4 ARE TOO LOW. ACCORDING TO SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED IN EXPOSURE "D". REVISE THE DESIGN
 PRESSURES TO CORRESPOND TO EXPOSURE "D".
 NOTE: PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE REVISED DESIGN PRESSURES ARE PROVIDED.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- ARCHITECT WHO IS SIGNING AND SEALING THE PLANS TO
 PROVIDE HIS INFORMATION IN THE TITLE BLOCK AS REQUIRED
 BY FAC 61G1-16.004 AND CHAPTER 481 F.S.
 NOTE: SEE BELOW FOR REQUIRED INFORMATION.
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
 RULEMAKING AUTHORITY 481.2055, 481.221(1), (3) FS. LAW
 IMPLEMENTED 481.219, 481.221(1), (3) FS. HISTORY?NEW
 9-7-00, AMENDED 3-16-14.
  
 4- CLARIFY WHERE IS THE FIBERGLASS DOOR FLORIDA PRODUCT
 APPROVAL FL15180.19 SUBMITTED GOING TO BE INSTALLED.
 PLANS SUBMITTED DON'T INCLUDE THIS DOOR. SEC. 107.2.1
 CITY AMENDMENTS.
  
 5- CLARIFY WHERE IS THE CASEMENT WINDOWS NOA 15-0519.13
 SUBMITTED GOING TO BE INSTALLED. PLANS SUBMITTED DON'T
 INCLUDE THIS DOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- CLARIFY WHERE IS THE HORIZONTAL ROLLING WINDOW NOA
 15-0519.09 SUBMITTED GOING TO BE INSTALLED. PLANS
 SUBMITTED DON'T INCLUDE THIS DOOR. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- CLARIFY TYPE OF DOOR TO BE INSTALLED IN MASTER
 BATHROOM AREA. STACKABLE DOOR OR SOLID DOOR. SEE FLOOR
 PLAN AND DOOR SCHEDULE ON SHEET A4 AND EXTERIOR
 ELEVATION ON SHEET A6. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) STACKABLE DOORS AS SHOWN ON PLANS FOR LIVING AND
 MASTER BATH AREA.
  
 B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 C) FRENCH DOOR AS SPECIFIED ON PLANS AND ELEVATION FOR
 THE EXISTING BATHROOM.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  
  
  