| Plan Review Notes For Permit 16020666 |
| Permit Number |
16020666 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-19 12:35:57 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. NOTE THAT A BUILDING PERMIT MUST BE ISSUED BEFORE WE | | | CAN PROCEED WITH THE ELECTRICAL REVIEW FOR THE SCOPE OF | | | WORK SHOWN. FBC 107 | | | 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|