2016-06-08 09:45:48808/820/906 GRANT STREET
 PERMIT #16020653
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE INSTALLATION OF 3 BACKFLOW
 PREVENTERS. THE 6-INCH BACKFLOW PREVENTER IS REQUIRED;
 HOWEVER, THE TWO OTHER 4-INCH BACKFLOW PREVENTERS SHALL
 BE REPLACED WITH POST INDICATOR VALVES (PIVS).
  
 PROVIDE JOINT RESTRAINT(TORQUE REQUIREMENTS) PRODUCT
 DATA ON-SITE FOR THE FIRE INSPECTOR.
  