| Plan Review Notes For Permit 16020653 |
| Permit Number |
16020653 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-06-08 09:45:48 | 808/820/906 GRANT STREET | | | PERMIT #16020653 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE THE INSTALLATION OF 3 BACKFLOW | | | PREVENTERS. THE 6-INCH BACKFLOW PREVENTER IS REQUIRED; | | | HOWEVER, THE TWO OTHER 4-INCH BACKFLOW PREVENTERS SHALL | | | BE REPLACED WITH POST INDICATOR VALVES (PIVS). | | | | | | PROVIDE JOINT RESTRAINT(TORQUE REQUIREMENTS) PRODUCT | | | DATA ON-SITE FOR THE FIRE INSPECTOR. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|