2016-06-08 10:08:131807/1851 DIVISION AVENUE & 838 ADAMS STREET
 PERMIT #16020652
  
 THE PLANS INDICATE THE INSTALLATION OF 5 BACKFLOW
 PREVENTERS. THE TWO 8-INCH BACKFLOW PREVENTERS ARE
 REQUIRED; HOWEVER, THE THREE OTHER 6-INCH BACKFLOW
 PREVENTERS SHALL BE REPLACED WITH POST INDICATOR VALVES
 (PIVS).
  
 PROVIDE JOINT RESTRAINT (TORQUE REQUIREMENTS) PRODUCT
 DATA ON-SITE FOR THE FIRE INSPECTOR.
  
 CONTRACTORS TYPE V STATE LICENSE EXPIRES 06/30/16
  
  
 WESLEY JOLIN - OFFICE OF THE FIRE MARSHAL - WPB FIRE