| Notes |
| Date |
Text |
| 2016-06-08 10:08:13 | 1807/1851 DIVISION AVENUE & 838 ADAMS STREET | | | PERMIT #16020652 | | | | | | THE PLANS INDICATE THE INSTALLATION OF 5 BACKFLOW | | | PREVENTERS. THE TWO 8-INCH BACKFLOW PREVENTERS ARE | | | REQUIRED; HOWEVER, THE THREE OTHER 6-INCH BACKFLOW | | | PREVENTERS SHALL BE REPLACED WITH POST INDICATOR VALVES | | | (PIVS). | | | | | | PROVIDE JOINT RESTRAINT (TORQUE REQUIREMENTS) PRODUCT | | | DATA ON-SITE FOR THE FIRE INSPECTOR. | | | | | | CONTRACTORS TYPE V STATE LICENSE EXPIRES 06/30/16 | | | | | | | | | WESLEY JOLIN - OFFICE OF THE FIRE MARSHAL - WPB FIRE | | | RESCUE | | | |
|