2016-02-24 10:08:461624 DOUGLAS AVENUE
 PERMIT #16020652
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES AN ADDRESS OF 1624
 DOUGLAS AVENUE HOWEVER THIS APPEARS TO BE INCORRECT.
 THE CORRECT ADDRESS MAY BE 808 OR 906 GRANT STREET OR
 1807 OR 1851 DIVSION AVENUE. PLEASE CONFIRM.
  
 NO ADDRESS PROVIDED ON THE SUBMITTED PLANS.
  
 ONLY ONE SET OF PLANS SUBMITTED.
  
 SUBMIT PRODUCT DATA CUT SHEETS FOR PIPE, FITTINGS,
 MECHANICAL RESTRAINTS, HYDRANTS, BACKFLOW PREVENTERS
 ETC. MECHANICAL JOINTS SHALL INDICATE THE PROPER TORQUE
 TO BE APPLIED TO THE BOLTS (IF APPLICABLE).
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT
 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING
 PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT
 PRESSURE +/-5 PSI FOR 2 HOURS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  