Plan Review Notes
Plan Review Notes For Permit 16020625
Permit Number 16020625
Review Stop B
Sequence Number 2
Notes
Date Text
2016-04-25 07:42:49RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 REQUIRED INFORMATION WILL BE PROVIDED AFTER THE PERMIT
 IS ISSUED AND BEFORE REQUESTING INSPECTIONS. FEES MAY
 APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) NEED THE NAME OF THE PERSON COMPLETING THE
 COMPLIANCE REPORT. AS REQUIRED BY SEC. R405.4.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) NEED THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) NEED THE EPL DISPLAY CARD SIGNED BY THE BUILDER AS
 REQUIRED BY SEC. R405.4.3 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 D) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM,
 INCLUDING THE NAME OF THE BUILDER. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 2- ICYNENE ICC EVALUATION REPORT SUBMITTED IS EXPIRED.
 PROVIDE CURRENT EVALUATION REPORT. AND ARCHITECT OF
 RECORD TO REVIEW/APPROVE REPORT PRIOR TO SUBMITTAL.
 SEC. R316 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SHEET S1.0: REVISE DESIGN PARAMETERS INFORMATION
 ITEM #5. WHAT DOES "ALL CALCULATIONS ARE BASED ON 2010"
 STANDS FOR? REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS. PLANS
 CALL FOR SOLID CORE METAL DOOR WITH RAISED PANELS.
 JELD-WEN DOOR INFORMATION SUBMITTED IS FOR STEEL DOOR
 WITH GLAZING. IT DOESN'T MATCH PLANS AND DOESN'T HAVE A
 FLORIDA PRODUCT APPROVAL NUMBER.
  
 B) ROOF SHINGLES AS SHOWN ON PLANS (REPEAT COMMENT).
  
 C) ROOF SELF ADHERED UNDERLAYMENT AS SPECIFIED ON THE
 TYPICAL WALL SECTIONS. NOA 13-0514.12 SUBMITTED IS FOR
 FLAT ROOF ASSEMBLIES. IT'S NOT A SELF ADHERED
 UNDERLAYMENT FOR SHINGLES.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS. FLORIDA
 PRODUCT APPROVAL FL158-R7 SUBMITTED IS INCOMPLETE .
 IT'S MISSING THE TECHNICAL DRAWINGS THAT WERE SUBMITTED
 FOR APPROVAL. PROVIDE COMPLETE INFORMATION.
  
 ***PLEASE PROVIDE REPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  