| Plan Review Notes For Permit 16020625 |
| Permit Number |
16020625 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-26 10:59:44 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | NOTE: MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. | | | REQUIRED INFORMATION WILL BE PROVIDED AFTER THE PERMIT | | | IS ISSUED AND BEFORE REQUESTING INSPECTIONS. FEES MAY | | | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | | PREFERRED AT THIS TIME. | | | | | | 1- CLARIFY/REVISE THE INFORMATION SHOWN ON SHEET M.1 | | | FOR BEDROOM #2 AIR SUPPLY GRILL . WHAT'S 168/109? | | | WHAT'S THE ACTUAL QUANTITY OF CFM'S ENTERING TO THIS | | | ROOM? WHAT'S THE SIZE OF THE GRILL?. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- PROVIDE THE NAME AND SIGNATURE OF PERSON RESPONSIBLE | | | FOR THE DESIGN. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD | | | DRAWINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|