| 2016-03-03 11:31:11 | JOB PERMIT NUMBER: 16020625 |
| | JOB ADDRESS: 308 COLONIAL RD |
| | WEST PALM BEACH FLORIDA |
| | DATE: MARCH 3 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - ADJUST AND RECONFIGURE ACCORDINGLY. LOAD CALCULATIONS |
| | SHOW SQUARE FOOTAGE AS 1766 AND SHEET SP1 STATES 2865 |
| | SQFT TOTAL ? FURTHERMORE SHOW ALL PANEL SCHEDULES AND |
| | SERVICE EQUIPMENT/PANELBOARDS LOCATIONS EXISTING & NEW |
| | ON FLOOR PLANS . WBA 107 |
| | - INSERT INTERSYSTEM BONDING ON RISER DIAGRAM AS WELL |
| | AS AIC RATINGS OF EQUIPMENT OCPD NEC 110.9, 110.10 NEC |
| | 250.94. EXISTING METER CAN LUGS MUST BE RATED FOR DUAL |
| | WIRE NEC 110.14 |
| | - INSULATIONS OF FEEDER CONDUCTORS IS SHOWN AS THHN |
| | WHICH IS NOT RATED FOR WET LOCATIONS NEC 300.5 , 300.7 |
| | . SEALING IS REQUIRED IF EXPOSED TO DIFFERENT |
| | TEMPERATURES. |
| | - ROMEX IS A BRAND NAME PROPER ELECTRICAL TERMINOLOGY |
| | IS NM CABLE PER NEC 334 |
| | - FAN BOXES MUST BE SECURED AND INSTALLED ACCORDING TO |
| | NEC 314.27 C |
| | - SMOKE / CARBON ALARMS REQUIRED PER RESIDENTIAL CODE |
| | SECTIONS 314 & 315 |
| | - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENCY , IC |
| | RATED, AND SEALED TO NOT COMPROMISE BUILDING THERMAL |
| | ENVELOPE. ( 2 CFM ) FBC ER 404.1.1 / 402.4.4 |
| | |
| | |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |