| 2016-03-14 11:27:00 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF THE PAID RECEIPT IF FEES ARE DUE. |
| | COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| | DEVELOPMENT CODE. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| | COMPLIANCE WITH SEC. R807 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- SPECIFY CARBON MONOXIDE ALARMS BY THE BEDROOMS AS |
| | REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). INCLUDING EXISTING BEDROOMS. |
| | |
| | 5- MASONRY GABLE WALL VERTICAL REINFORCEMENT SPACING TO |
| | COMPLY WITH SEC. R609.4.2 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). REVISE PLANS AS REQUIRED. |
| | |
| | 6- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE |
| | FOAM INSULATION SPECIFIED ON PLANS. ARCHITECT OF RECORD |
| | TO REVIEW/APPROVE REPORT PRIOR TO SUBMITTAL. |
| | |
| | 7- SHEET S1.0: REVISE DESIGN PARAMETERS INFORMATION. |
| | WHAT DOES "ALL CALCULATIONS ARE BASED ON 2010" STANDS |
| | FOR? REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 8- SHEET S2.0: |
| | A) UPDATE THE BUILDING CODE SPECIFIED ON THE |
| | ENGINEERING CRITERIA AND TRUSS DESIGN CRITERIA. |
| | REFERENCE CURRENT CODE. CHAPTER 553 F. S. |
| | |
| | B) REVISE THE BOTTOM CHORD LIVE LOAD. SEE NOTES "B" AND |
| | "G" OF TABLE R301.5 AND REVISE AS REQUIRED. |
| | |
| | C) REVISE DESIGN PARAMETERS INFORMATION. WHAT DOES "ALL |
| | CALCULATIONS ARE BASED ON 2010" STANDS FOR? REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 9- SHEET S3.0: UPDATE THE DESIGN PARAMETERS AND |
| | CASCRETE PERIMETER BEAM SYSTEM UPLIFT CALCULATIONS |
| | INFORMATION. REFER TO THE CURRENT 2014 CODE. CHAPTER |
| | 553 F.S. |
| | |
| | 10- SPECIFY HOW COMPLYING WITH THE HEATING REQUIREMENTS |
| | OF SEC. R303.9 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 11- CLARIFY IF THE SOFFIT VENT SPECIFIED ON THE EAST |
| | ELEVATION ON SHEET A2.0 IS A DECORATIVE VENT OR WORKING |
| | VENT. IF WORKING VENT, THEN PRODUCT APPROVAL (2 COPIES) |
| | IS REQUIRED BY FAC 61G20-3.002(33. |
| | |
| | 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) DOUBLE FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS |
| | AND THAT MEETS THE CALCULATED DESIGN PRESSURES. |
| | NOTE: FLORIDA FL7630.2 PRODUCT APPROVAL SUBMITTED IS |
| | FOR SINGLE DOOR WITH SIDELITE AND IT DOESN'T MEET THE |
| | DESIGN PRESSURES CALCULATED BY THE ARCHITECT ON SHEET |
| | S2.0. |
| | |
| | B) GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS. |
| | |
| | C) SOFFIT VENT. SEE ITEM #11 ABOVE. |
| | |
| | D) ROOF SHINGLES AS SHOWN ON PLANS. |
| | |
| | E) ROOF SELF ADHERED UNDERLAYMENT AS SPECIFIED ON THE |
| | TYPICAL WALL SECTIONS. |
| | |
| | F) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |