Plan Review Notes
Plan Review Notes For Permit 16020622
Permit Number 16020622
Review Stop G
Sequence Number 1
Notes
Date Text
2016-02-18 06:11:081.) WHAT IS THE APPROXIMATE BTU LOAD FOR THE FUTURE
 GRILL? USE THE BTU LOAD FOR A BARBECUE FROM TABLE 402.2
 OF THE 2014 FUEL GAS CODE.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 3) INCLUDE THE POOL HEATER IN THE DESCRIPTION OF WORK
 ON THE PERMIT APPLICATION. 2014 FBC SEC. 107.2.1.
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 5) SUBMIT COPIES OF THE APPLICABLE SIZING TABLE FROM
 THE 2014 FUEL GAS CODE THAT WAS USED IN THE SIZING OF
 THIS SYSTEM. FBC SEC. 107.2.1.
 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED.
 7) COPPER SHALL NOT BE USED IF THE GAS CONTAINS MORE
 THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN SULFIDE PER
 100 STANDARD CUBIC FEET OF GAS PER 2014 FGC
 SEC.403.4.3. SUBMIT DOCUMENTATION FROM THE GAS PURVEYOR
 SHOWING THE CONCENTRATION OF HYDROGEN SULFIDE OF THE
 GAS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  